Terminal And Cable Entry Data For The Power Cables; Terminal Data For The Supply And Inverter Control Units; Electrical Power Network Specification - ABB ACS880-37LC-0390A-7 Hardware Manual

Industrial drives
Table of Contents

Advertisement

184 Technical data

Terminal and cable entry data for the power cables

The locations and sizes of the cable entries are shown in the dimension drawings delivered
with the drive, and the dimension drawing examples in this manual.
Busbar terminal material: Tin-plated copper.

Terminal data for the supply and inverter control units

See chapter
Control units of the drive (page

Electrical power network specification

Voltage (U
)
1
Network type
Frequency
Imbalance
Short-circuit withstand
strength (IEC/EN 61439-1)
Short-circuit withstand
strength for supply unit with
100 kA input unit (option
+F274) (IEC/EN 61439-1)
Short-circuit current protec-
tion (UL 508A, CSA C22.2
No. 14-13)
Fundamental power factor
(cos phi
)
1
690 V units: 525...690 V AC 3-phase ± 10% (525...600 V AC ± 10% in UL/CSA
installations, or corner-grounded TN systems). This is indicated in the type desig-
nation label as typical input voltage levels (3~ 525/600/690 V AC).
TN (grounded) and IT (ungrounded) systems
50/60 Hz, variation ± 5% of nominal frequency
Max. ± 3% of nominal phase-to-phase input voltage
With main circuit breaker (option +F255) and without grounding/earthing switch
(without option +F259):
Rated peak withstand current (I
Rated short-time withstand current (I
All other configurations:
Rated peak withstand current (I
Rated short-time withstand current (I
Rated peak withstand current (Ipk): 220 kA
Rated short-time withstand current (Icw): 100 kA/1 s
Note: Options +F259 and +F274 are mutually exclusive for some drive types.
Consult ABB for availability.
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when the input cable is
protected with class T fuses.
0.99
117).
): 143 kA
pk
): 65 kA/1 s
cw
): 105 kA
pk
): 50 kA/1 s
cw

Advertisement

Table of Contents
loading

Table of Contents