Dc Power Cables - Output To Cable Reel - ABB HVC-C 100-150 kW Installation Manual

Table of Contents

Advertisement

Parameter
Cross section range (maximum)
Diameter
Maximum length between the power
cabinet and the control box
Conductor
Diameter of the phase conductors
Insulation
Nominal voltage Uo/U
Minimum test voltage
Ambient temperature range
Strip length
20.12.5

DC power cables - output to Cable Reel

Parameter
Type
Number of cores
Diameter range (minimum)
Diameter range (maximum)
Maximum length between the
control box and Cable Reel
Conductor
Diameter of the phase conductors
Insulation
Nominal voltage Uo/U
Minimum test voltage
Ambient temperature range
Strip length 11 mm
6AGA000007-0611-EN | 001
Note:
Calculate the cable cross-section to guarantee the voltage drop
below 10V. If the voltage drop is above 7V, consult the manufacturer.
If the length of the cables between the power cabinet and the control
box is between 100 and 150 m, you need to install a long-distance
package. The long-distance package is included in a separate manual.
Ask the manufacturer.
Specification
185 mm²
22 - 32 mm
100 m
Stranded in tin plated copper or alumi-
num,fine wired, stranded according to VDE
0295 cl.5/IEC Cl.5
Refer to the local rules.
Rubber or PVC that is serviceable for out-
door use, UV-protected, and oil resistant
600/1000 Vac - 900/1500 Vdc
6 kV
-40 ºC to 80 ºC, permissible conductor oper-
ating temperature +90 °C
11 mm
Specification
1x positive, 1x negative cable
1x earth cable
3x70 mm²
44 mm
57 mm
5 m
Stranded in tin plated copper or alumi-
num,fine wired, stranded according to VDE
0295 cl.5/IEC Cl.5
Refer to the local rules.
Rubber or PVC that is serviceable for out-
door use, UV-protected, and oil resistant
600/1000 Vac - 900/1500 Vdc
6 kV
-40 ºC to 80 ºC, permissible conductor oper-
ating temperature +90 °C
Technical data