One, two or three Pt100, Pt1000 or PTC sensors; or one KTY84 sensor
2
Set the input type to voltage with the appropriate switch or jumper on the control unit. Make the corres-
ponding setting in the control program in parameter group 12 Standard AI.
3
Select the excitation mode in parameter group 13 Standard AO.
WARNING!
As the inputs pictured above are not insulated according to IEC/EN 60664, the
connection of the motor temperature sensor requires double or reinforced insulation
between motor live parts and the sensor. Make sure that the current does not exceed
the maximum allowed current through the Pt100/Pt1000 sensor.

DIIL input

The DIIL input is used for the connection of safety circuits. The input is parametrized to stop
the unit when the input signal is lost.
Note: This input is NOT SIL or PL certified.

The XD2D connector

The XD2D connector provides an RS-485 connection that can be used for
basic master/follower communication with one master drive and multiple followers,
fieldbus control through the embedded fieldbus interface (EFB), or
drive-to-drive (D2D) communication implemented by application programming.
See the firmware manual of the drive for the related parameter settings.
Enable bus termination on the units at the ends of the drive-to-drive link. Disable bus
termination on the intermediate units.
Use shielded twisted-pair cable with a twisted pair for data and a wire or another pair for
signal ground (nominal impedance 100 ... 165 ohm, for example Belden 9842) for the wiring.
For best immunity, ABB recommends high quality cable. Keep the cable as short as possible.
Avoid unnecessary loops and parallel runs near power cables such as motor cables.
The following diagram shows the wiring between control units.
T
T
AI1+
2
AI1-
...
AO1
3
AGND