Default I/O Diagram Of The Inverter Control Unit (A41) - ABB ACS880-37LC-0390A-7 Hardware Manual

Industrial drives
Table of Contents

Advertisement

Default I/O diagram of the inverter control unit (A41)

The table below describes the use of the connections in the inverter unit. Under normal
circumstances, the factory-made wiring should not be changed.
The wire size accepted by all screw terminals (for both stranded and solid wire) is
2
0.5 ... 2.5 mm
(22...12 AWG). The tightening torque is 0.45 N·m (4 lbf·in).
Terminal
XD2D
1
B
1
2
2
A
3
3
BGND
4
4
Shield
D2D.TERM
X485
5
B
5
6
6
A
7
7
BGND
8
8
Shield
XRO1, XRO2, XRO3
11
NC
11
12
COM
12
13
NO
13
21
NC
21
22
22
COM
23
23
NO
31
31
NC
32
32
COM
33
33
NO
XSTO, XSTO OUT
1
OUT
1
2
SGND
2
3
IN1
3
4
4
IN2
5
5
IN1
6
6
SGND
7
7
IN2
8
8
SGND
XDI
Description
Drive-to-drive link
Drive-to-drive link. Refer to section
Drive-to-drive link termination switch. Must be set to ON when the inverter unit
is the first or last unit in the drive-to-drive (D2D) link. On intermediate units, set
termination to OFF.
RS485 connection
Not in use by default
Relay outputs
Norm. closed
Common
Norm. open
Norm. closed
Common
Norm. open
Norm. closed
Common
Norm. open
Safe torque off
XSTO: Factory connection. Both circuits must be closed for the drive to start
(IN1 and IN2 must be connected to OUT). Refer to chapter
function.
XSTO OUT: Safe torque off output to inverter modules.
Digital inputs
Control units of the drive 123
The XD2D connector (page
XRO1: Ready (Energized = Ready)
250 V AC / 30 V DC, 2 A
XRO2: Running (Energized = Running)
250 V AC / 30 V DC, 2 A
XRO3: Fault (-1) (Energized = No fault)
250 V AC / 30 V DC, 2 A
The Safe torque off
128).