Harmonic distortion

Motor connection data

Motor types
Voltage (U
)
2
Frequency (f
)
2
Current
Switching frequency
Maximum recommended
motor cable length
Relay contact data for control of external main
contactor/breaker

General

The external main contactor or breaker is controlled by the drive through relay K3. The relay
has one normally-open (NO) and one normally-closed (NC) contact.
Emergency stop options add a relay (K62) to the drive. To trip the main breaker upon an
emergency stop, one of the output switchover contacts of the relay must be wired to the
undervoltage coil.
Harmonics are below the limits defined in IEEE519.
R
sc
20
100
1) Other loads may influence the THD value.
THD = Total Harmonic Distortion (THD). The voltage THD depends on the short-
circuit ratio (R
). The spectrum of the distortion also contains interharmonics.
sc
R
= I
/I
sc
sc
N
I
= short-circuit current at point of common coupling (PCC)
sc
I
= supply unit nominal current
N
th
I
= n
harmonic current component
n
Asynchronous AC induction motors, permanent magnet synchronous motors and
AC induction servomotors, ABB synchronous reluctance (SynRM) motors
0 ... U
, 3-phase symmetrical, U
1
0...500 Hz
• For higher operational output frequencies, please contact your local ABB repres-
entative.
• Operation outside the range of 12...150 Hz requires derating. See the derating
information.
See the rating tables.
3 kHz (typical). The switching frequency can vary per frame and voltage. For exact
values, contact your local ABB representative.
500 m (1640 ft).
Note: Longer cables cause a motor voltage decrease which limits the available
motor power. The decrease depends on the motor cable length and characteristics.
Contact ABB for more information.
Note: With motor cables longer than 150 m (492 ft) the EMC Directive requirements
may not be fulfilled.
THD Voltage [%]
3
0.8
at the field weakening point
max
Technical data 185
THD Current [%]
1)
2.5
2.5 (4.0 with types
1)
-0390A...-0520A-7)