44 Operation principle and hardware description
firmware manual for parameter settings
ATEX-certified motor thermal protection functions for cabinet-built ACS880 drives
(options +L513+Q971 and +L514+Q971) user's manual (3AXD50000014979 [English])
Pt100 relay alarm and trip limit setting instructions in the start-up instructions
circuit diagrams delivered with the drive for the actual wiring.
Starter for auxiliary motor fan (options +M600...M610)

What the option contains

The option provides switched and protected connections for 3-phase auxiliary motor fans.
Each fan connection is equipped with:
fuses
a manual motor starter switch with an adjustable current limit
a contactor controlled by the drive, and
terminal block X601 for customer connections.

Description

The output for the auxiliary fan is wired from the 3-phase supply voltage to terminal block
X601 through a motor starter switch and a contactor. The contactor is operated by the drive.
The 230 V AC control circuit is wired through a jumper on the terminal block; the jumper
can be replaced by an external control circuit.
The starter switch has an adjustable trip current limit, and can be opened to permanently
switch the fan off.
The statuses of both the starter switch and the fan contactor are wired to the terminal block.
See the circuit diagrams delivered with the drive for the actual wiring.