Start-up

Contents of this chapter

This chapter contains the start-up and switch-off procedures of the drive.

Start-up procedure

The tasks which are needed in certain cases only are marked with underlining, and option
codes are given in brackets. Default device designations (if any) are given in brackets after
the name, for example "main switch-disconnector [Q1]". The same device designations are
also used in the circuit diagrams.
These instructions cannot and do not cover all possible start-up tasks of a customized drive.
Always refer to the delivery-specific circuit diagrams when proceeding with the start-up.
WARNING!
Only qualified electrical professionals are permitted to do the work described in this
chapter.
Note: For certain options (such as functional safety options +Q950, +Q951, +Q952, +Q957,
+Q963, +Q964, +Q978, +Q979), additional start-up instructions are given in their separate
manuals.
Action
Safety
WARNING!
Obey the safety instructions during the start-up procedure. See chapter
tions (page
15).
Checks/Settings with no voltage connected
Make sure that the disconnector of the supply transformer is locked to the off (0) position, ie. no voltage
is, and cannot be connected to the drive accidentally.
Start-up 137
9
Safety instruc-
12