Terminal And Entry Data For The Power Cables - ABB ACS880-34 drive Quick Installation And Start-Up Manual

Drive modules (132 to 400 kw, 200 to 450 hp)
Hide thumbs Also See for ACS880-34 drive:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
282 Technical data and references
1)
IEC
ACS880-
Cu cable type
34-...
2
mm
U
= 500 V
n
240A-5
1 × (3 × 120)
260A-5
2 × (3 × 50)
302A-5
2 × (3 × 70)
361A-5
2 × (3 × 120)
414A-5
3 × (3 × 50)
460A-5
3 × (3 × 70)
503A-5
3 × (3 × 95)
U
= 690 V
n
142A-7
1 × (3 × 70)
174A-7
2 × (3 × 50)
210A-7
2 × (3 × 50)
271A-7
2 × (3 × 70)
330A-7
2 × (3 × 50)
370A-7
3 × (3 × 70)
430A-7
3 × (3 × 70)
1) The cable selection is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top
of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F) (EN 60204-1 and
IEC 60364-5-52). For other conditions, select the cables according to local safety regulations, appropriate input
voltage and the load current of the drive.
2) The cable selection is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C (104 °F)
ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly buried).
For other conditions, dimension the cables according to local safety regulations, appropriate input voltage and
the load current of the drive.

Terminal and entry data for the power cables

Maximum accepted
cable size
Screw size for connect-
ing busbars to the drive
module input and output
busbars
Tightening torque
Protection classes for module
Degrees of protection
(IEC/EN 60529)
Enclosure types (UL
50/50E)
Overvoltage category
(IEC/EN 60664-1)
Protective class
(IEC/EN 61800-5-1)
Al cable type
2
mm
2 × (3 × 70)
3 × (3 × 70)
3 × (3 × 70)
300 MCM or 2 × 1/0
3 × (3 × 70)
350 MCM or 2 × 2/0
2 × (3 × 150)
500 MCM or 2 × 3/0
3 × (3 × 120)
700 MCM or 2 × 4/0 or 3 × 2/0
3 × (3 × 120)
2 × 250 MCM or 3 × 2/0
2 × (3 × 50)
2 × (3 × 50)
2 × (3 × 70)
3 × (3 × 50)
300 MCM or 2 × 1/0
2 × (3 × 120)
400 MCM or 2 × 2/0
2 × (3 × 150)
500 MCM or 2 × 3/0
2 × (3 × 185)
700 MCM or 2 × 4/0 or 3 × 2/0
2
4 × (3 × 240) mm
or 4 × (3 × 500 MCM)
M12
50...75 N·m (37...55 lbf·ft)
IP20 (standard)
IP00 (option +0B051)
UL Open Type
III
I
US
Cu cable type
AWG/kcmil
3/0
250 MCM or 2 × 1
1/0
2/0
4/0
2)
Al cable type
AWG/kcmil
250 MCM or 2 × 1
350 MCM or 2 × 2/0
500 MCM or 2 × 3/0
500 MCM or 2 × 3/0
700 MCM or 2 × 4/0 or 3 × 2/0
2 × 300 MCM or 3 × 3/0
2 × 400 MCM or 3 × 4/0
3/0
4/0
300 MCM or 2 × 1/0
400 MCM or 2 × 2/0
600 MCM or 2 × 4/0 or 3 × 1/0
700 MCM or 2 × 4/0 or 3 × 2/0
2 × 300 MCM or 3 × 3/0