Alpha ESS Storion-SMILE5 Installation, Operation & Maintenance Manual page 17

Energy storage system
Hide thumbs Also See for Storion-SMILE5:
Table of Contents

Advertisement

A SMILE5 installed in any corridor, hallway, lobby or the like and leading to an emergency exit shall
ensure sufficient clearance for safe egress of at least 1 meter.
The SMILE5 must also not be installed in potentially explosive atmospheres for gas cylinders that are
heavier than air gases and have a vent clamp in accordance with AS / NZS 3000.
2.1.3
Barrier to habitable rooms
To protect against the spread of fire in living spaces where the SMILE5 is mounted or on surfaces of a
wall or structure in living spaces with a SMILE5 on the other side, the wall or structure shall have a
suitable non-combustible barrier. If the mounting surface itself is not made of a suitable non-
combustible material, a non-combustible barrier can be placed between the SMILE5 and the surface
of a wall or structure.
If the SMILE5 is mounted at a wall or at a distance of 300 mm from the wall or structure separating it
from the habitable space, the distances to other structures or objects must be increased. The following
distances must then remain free:
(i)
600 mm beside the SMILE5;
(ii)
900 mm above the SMILE5; and
(iii)
600 mm before the SMILE5.
If the distance between the Storion-SMILE5 and
the ceiling or any object above the system is
less than 900 mm, the ceiling or structural
surface above the system must be made of non-
combustible material within a radius of 600 mm
around the system.
The SMILE5 must be mounted so that the
highest point is not more than 2.2 m above the
ground or the platform.
___________________________________________________________________
Installation
Figure 9 Limit Distance of Installation to
Alpha ESS Co., Ltd.
Your Smart Energy
Neighboring Objects
Page 15

Advertisement

Table of Contents
loading

Table of Contents