Advertisement

OPTIWAVE 7300 C
Error Message
Peak and spectrum
Spectrum quality is bad
Empty spectrum is invalid
Plausible peak is not
available
Software error
Unable to load DSP firmware
01/2008 • 4000172401 - HB OPTIWAVE 7300 R03 en
Error
code
Description
W
The quality of the spectrum is
poor. If this message is
temporarily shown, this will
not affect the performance of
the instrument. If this
message is continuously
shown, the measured values
can be incorrect. The error
message "Measurement is
old" will then be displayed.
Possible causes are foam,
vortices, turbulent product
surface and internal tank
elements.
W
The Empty Spectrum stored
in the instrument does not
agree with the installation. If
you change the instrument
configuration (tank height
etc.), this message will be
displayed. The recorded
empty spectrum will not be
used by the instrument while
this error message is
displayed.
W
The signal peak is not found
within the measuring window
that filters the signals
returning to the antenna. The
measurement is not correct.
The instrument will
automatically increase this
window to find the correct
signal.
E
The download of the DSP
Firmware did not download
correctly to the DSP board.
www.krohne.com
OPERATION
Corrective action
Check the installation and the
process. Reconfigure the
instrument and record a new
empty spectrum. If
necessary, contact the
supplier.
Check the installation and the
process. Reconfigure the
instrument and record a new
empty spectrum. If
necessary, contact the
supplier.
Check the installation and the
process. Reconfigure the
instrument and record a new
empty spectrum. If
necessary, contact the
supplier.
Restart the instrument. If the
problem continues, contact
the supplier.
6
79