KROHNE OPTIWAVE 7300 C Handbook page 25

Non-contact radar fmcw level meter
Hide thumbs Also See for OPTIWAVE 7300 C:
Table of Contents

Advertisement

OPTIWAVE 7300 C
The bypass chamber must have a process connection that is below the lowest measured
level of liquid.
Installation next to tanks containing more than one liquid
The bypass chamber must have a process connection that is above the maximum level of
liquid.
The bypass chamber must have a process connection that is below the lowest measured
level of liquid.
There must be more process connections along the length of the bypass chamber. These
must have a minimum diameter of 25 mm/1" with a minimum distance of 100 mm/4" between
the holes.
Installation recommendations for bypass chambers that contain more than one liquid
Figure 3-13:
1
Bypass chamber
Distance between holes 100 mm/4"
2
Hole diameter Ø25 mm/1"
3
01/2008 • 4000172401 - HB OPTIWAVE 7300 R03 en
1
2
3
www.krohne.com
INSTALLATION
3
25