If the instrument is for a horizontal cylindrical tank, we recommend that you install it in a stilling
well.
Horizontal cylindrical tanks
Figure 3-11:
The instrument is installed without a stilling well. There are multiple reflections. Refer to the CAUTION! that follows.
1
The instrument is installed in a stilling well and measures correctly.
2
CAUTION!
If the instrument is installed in horizontal cylindrical tank without a stilling well, do not put it on
the tank centerline. This will cause multiple reflections and the instrument will not measure
accurately. Use the multiple reflections function in supervisor mode > advanced setup >
Installation setup to keep the effects of multiple reflections to a minimum. For more data, refer
to C. Advanced setup
01/2008 • 4000172401 - HB OPTIWAVE 7300 R03 en
on page 60.