Quick-start
©
KROHNE 04/2004
CH
General
This is a quick-start guide only. For further infor-
mation please consult the handbook, data sheet,
special manuals and certificates supplied on
CD-ROM.
Installation, assembly, commissioning and ser-
vicing must only be undertaken by trained
personnel. Maintenance which is considered
relevant to safety in the sense of explosion pro-
tection must only be carried out by the manu-
facturer, his agents or under the supervision of
experts.
For use in hazardous areas, special codes and
regulations are applicable, which are supplied in
a separate document that describes all ATEX
hazardous area information.
Responsibility as to suitability and intended use
of this device rests solely with the user. The sup-
plier does not accept any liability resulting from
misuse by the customer. Improper installation
and operation of our level gauges may lead to
loss of warranty. In addition, the "General condi-
tions of sale", found on the back of the invoice
and forming the basis of the purchasing con-
tract, are applicable.
If you need to return the device to the manufac-
turer or supplier, please complete the form
given on the CD-Rom and attach to the device.
KROHNE regrets that it cannot repair or check
your device unless accompanied by this com-
pleted form.
7.02287.21.00
OPTIWAVE 7300 C
Radar Level Meter
Measurement of distance,
level and volume of liquids,
pastes and solids
• Easy installation
• Wizard driven
• Service and maintenance-free
Items supplied
*
*If applicable
Visual check

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the OPTIWAVE 7300 C and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for KROHNE OPTIWAVE 7300 C

  • Page 1 If you need to return the device to the manufac- turer or supplier, please complete the form given on the CD-Rom and attach to the device. KROHNE regrets that it cannot repair or check your device unless accompanied by this com- pleted form.
  • Page 2: Quick Start

    Quick-start OPTIWAVE 7300 C Handling and installation instructions Antenna must protrude from nozzle base. max. 2°...
  • Page 3: Handling And Installation Instructions

    Handling and installation instructions Option max. 150°C / 300°F min. -40°C / -40°F Viton min. -20°C / -5°F Kalrez +80°C / +175°F -40°C / -40°F Install away from entry pipe. DN 40 / 50: Mount off-centre > 1/7 H, but max. 1/3 D to avoid multiple reflections.
  • Page 4: Special Considerations

    Special considerations Stray Avoid too many objects reflections ! near to the radar beam in tank. Stilling wells and bypass chambers Too many objects in tank: use bypass chamber Foam: use stilling well...
  • Page 5: Dimensions And Weights

    Dimensions and Weights Flange (Antenna DN 80) Antenna DN 80 with antenna extension approx. 11 kg /24.3 lb approx. 12 kg /26.5 lb Note: Additional antenna extension of 105 mm / 4.1" length available.
  • Page 6 Dimensions and Weights Flange (Antenna DN 40/50) Thread Dimensions in mm and inch Antenna type mm / inch mm / inch mm / inch 39 / 1.5 38.5 / 1.5 343.8 / 13.5 Antenna DN 40 43 / 1.7 50 / 2 355.3 / 14 Antenna DN 50 Note:...
  • Page 7: Wiring Options

    Terminal Compartment and Terminals Wiring options HART ® Non-Ex Configuration Software HART ® Modem min.250Ω L – Connection procedure • Unscrew terminal compartment cover. • Wire up using standard procedures. ® HART Explosion Proof (XP) / Ex d • Apply grease to thread Configuration Software of cover before closing.
  • Page 8: Technical Data Extract

    IS class I Div. 1 Gr. A...G; XP class I Div. 1 Gr. A…G IS class I Div. 1 Gr. A...G; XP class I Div. 1 Gr. A…G For futher data see data sheet, approvals and handbook on CD-ROM Hotline: +33(0)4.75.05.44.00 · Fax: +33(0)4.75.05.44.97 www.krohne.com for local contacts · E-mail: level@krohne.fr...
  • Page 9: Human Interface

    Human interface Normal mode: Selects type of Normal mode: information Selects display style. displayed. Program mode: Program mode: Moves cursor to right or Moves menu selects next menu level. selector up the list or increments parameter value. Program mode: Saves or confirms Normal mode: parameter.
  • Page 10: Start-Up Procedure

    Human interface Hot keys Mode Hot key activated when: Action Normal Enters program mode ☞ 3 seconds Saves current function Program used as quick link ☞ Active screen stored as Normal 3 seconds default screen ☞ HMI will reset to default All modes 3 seconds language...
  • Page 11: Setup Procedure

    Setup procedure Press 3 sec Complete Normal Mode Program Mode Installation Quick setup Empty Spectrum Test Advanced setup Conversion Service Output Quick link #1 Quick links The customer can assign Quick link #2 any menu point to one of the quick links (including Quick link #3 overwriting factory presets) Quick link #4...
  • Page 12 Setup procedure 1. Installation type 2. Tank height 3. Measuring range 4. Application type 5. Stillwell diameter* 1. Conversion wizard type 6. Blocking distance 2. Length unit 7. Settings summary 3. Density of product 1 (yes or no) 8. Save ? 4.

Table of Contents