CAUTION!
Installation requirements
The stilling well must be electrically conductive.
The inside diameter of the bypass chamber must not be more than 5 mm / 0.2" over the
diameter of the antenna (for a high-dielectric constant liquid).
The stilling well must be straight.
The stilling well must have a surface roughness of
There must be no sudden changes in internal diameter greater than 1 mm.0.04".
The bottom of the stilling well must be open.
Installation in tanks containing one liquid and foam
Drill a pressure equalization hole in the stilling well above the maximum level.
Deburr the hole.
Installation in tanks containing one liquid without foam
Drill a pressure equalization hole in the stilling well above the maximum level of the top liquid.
Drill more holes along the length of the stilling well. The holes have a minimum diameter of
10 mm/0.4" with a minimum distance of 100 mm/4" between the holes.
These holes help the liquid to move freely.
i
Deburr the holes.
01/2008 • 4000172401 - HB OPTIWAVE 7300 R03 en
0.1 mm/0.004".
±