KROHNE OPTIWAVE 7300 C Handbook page 63

Non-contact radar fmcw level meter
Hide thumbs Also See for OPTIWAVE 7300 C:
Table of Contents

Advertisement

OPTIWAVE 7300 C
Menu No.
C.1.22
C.2
C.3
C.3.1
C.3.2
C.3.3
C.3.4
C.3.5
C.3.6
C.4
C.4.1
C.4.2
C.4.3
C.4.4
C.4.5
01/2008 • 4000172401 - HB OPTIWAVE 7300 R03 en
Function
Function description
linearisation
The instrument uses this
table
table to increase on-site
accuracy. Give the number of
entries plotted. Fill the tank.
Make a reference
measurement and type in the
correct value next to the
instrument reading.
I/O
For fieldbus. Not yet
available.
output 1
(HART)
output function
Select an output function to
scale the current values . This
is not displayed in the
operator mode.
4 mA setting
Give a measurement value to
4 mA.
20 mA setting
Give a measurement value to
20 mA.
output range
Sets the effective range of
output 1 either with or
without over-run.
error handling
Sets the behaviour of current
output 1 if an error occurs.
error handling
The time after which the
delay
instrument shows there is a
measurement error.
HART address
any HART
than 0 will activate HART
multidrop mode. The current
output stays constant at
4 mA.
output 2
(passive)
output function
Select an output function to
scale the current values . This
is not displayed in the
operator mode.
4 mA setting
Give a measurement value to
4 mA.
20 mA setting
Give a measurement value to
20 mA.
output range
Sets the effective range of
output 1 either with or
without over-run.
error handling
Sets the behaviour of current
output 1 if an error occurs.
Number of entries min.-max:
0...50
level; distance; volume/mass;
ullage volume; reflection
min.-max: depends on other
functions. Refer to the
dependency tables below.
min.-max: depends on other
functions. Refer to the
dependency tables below.
min.-max: 3.8...20.5 mA
(NAMUR), 4...20 mA
3.6 mA, 22 mA, Hold
min.-max: 0...900 seconds
min.-max: 0...15
®
address greater
®
level; distance; volume/mass;
ullage volume; reflection
min.-max: depends on other
functions. Refer to the
dependency tables below.
min.-max: depends on other
functions. Refer to the
dependency tables below.
min.-max: 3.8...20.5 mA
(NAMUR), 4...20 mA
3.6 mA, 22 mA, Hold
www.krohne.com
OPERATION
Selection list
0
level
0 m / 0 ft
depends on
the output
function
4...20 mA
22 mA
10 seconds
0
level
0 m / 0 ft
depends on
the output
function
4...20 mA
22 mA
6
Default
63