KROHNE OPTIWAVE 7300 C Handbook page 61

Non-contact radar fmcw level meter
Hide thumbs Also See for OPTIWAVE 7300 C:
Table of Contents

Advertisement

OPTIWAVE 7300 C
Menu No.
C.1.8
C.1.9
C.1.10
C.1.11
C.1.12
C.1.13
C.1.14
01/2008 • 4000172401 - HB OPTIWAVE 7300 R03 en
Function
Function description
overfill
If this function is switched on,
detection
the instrument will monitor
the level even if it is in the
blocking distance. The
displayed output stays fixed at
the blocking distance, but an
error message will warn the
user that the tank is
overfilling.
blocking
The distance from the flange
distance
to the top limit of the
measuring range. If the
distance is less than the
blocking distance, the
instrument continues to
display the blocking distance.
reference
Offset relating to a reference
offset
location (distance). This value
is positive when the reference
location is above the device
flange face and negative if
below.
tank bottom
Offset relating to a reference
offset
location (level). The device
reference point for this
parameter is the bottom of
the tank (set in menu item
C.1.2.0). This value is positive
when the reference location
is below the tank bottom and
negative if above.
time constant
Using this function, the device
processes several
measurement readings to
filter out disturbances.
Increasing the time constant
will smoothen the integrated
readings, decreasing will
roughen the readings.
measuring
The instrument uses the
mode
dielectric constant of the tank
contents to monitor level. If
Er is low and the bottom of
the tank is flat, select "TBF
partial" mode. If you install
the instrument in a process
tank, select "TBF full". For
other uses, select "direct
measuring"
product Er
The instrument automatically
calculates the level based on
the product ε
"TBF partial" or "TBF full" in
item C.1.13, you can change
this value manually to adjust
readings.
yes; no
min-max:
0.220 m...tank height /
0.72 ft...tank height
min-max:
-tank height...50 m /
-tank height...164.05 ft
min-max:
-tank height...3000 m /
-tank height...9843 ft
min-max: 1...100 seconds
direct measuring; TBF
partial; TBF full
min-max: 1.01...99.90
. If you select
r
www.krohne.com
OPERATION
Selection list
no
0.3 m / 1 ft
0 m / 0 ft
0 m / 0 ft
3 seconds
direct
measuring
4
6
Default
61