Error - Cause - Error Correction - Eaton D64RP410 Manual

Grownd fault relay
Table of Contents

Advertisement

Function 4: Reset to factory settings/Reset parameters
60000
Function
Uint16 2
selection
60001
Pattern value
Uint16 2
part 1
60002
Pattern value
Uint16 2
part 2
60003
Type of reset Uint16 2
Function 6: Test
60000
Function
Uint16 2
selection
60001
Pattern value
Uint16 2
part 1
60002
Pattern value
Uint16 2
part 2
60003
Type of test
Uint16 2
Function 7: Reset
60000
Function
Uint16 2
selection
60001
Pattern value
Uint16 2
part 1
60002
Pattern value
Uint16 2
part 2
60003
Type of reset Uint16 2
WO
4
N/A
→ Selection
of "Reset to
factory
settings/Reset
parameters"
function
WO
62663
N/A
→ Security
pattern must be
written
for the function
to be executed
WO
1304
N/A
→ Security
pattern must be
written
for the function
to be executed
WO
1
N/A
→ Reset to
factory settings
excluding
interface
parameters
2
→ Reset to
factory settings
including
interface
parameters
WO
6
N/A
→ Selection
of the "Test"
function
WO
32343
N/A
→ Security
pattern must be
written for the
function to be
executed
WO
0
N/A
→ Security
pattern must be
written for
the function to
be executed
WO
3
N/A
→ Start RCM
test
WO
7
N/A
→ Selection of
"Reset" function
WO
13623
N/A
→ Safety
pattern must be
written for the
function to be
executed
WO
0
N/A
→ Security
pattern must be
written for the
function to be
executed
WO
1
N/A
→ Reset of the
alarm message
when fault
memory is
enabled
GROWND FAULT RELAY D64RP410 IL54032 September 2023 www.eaton.com
6 Error – Cause – Error correction
6 Error – Cause – Error correction
Error pattern Cause
RS-485
Unstable
Missing termination
system
due to incorrect
commissioning
or defective
component.
No device is
terminated.
Faulty termination
due to incorrect
configuration
or defective
component. Only
one or more than
two devices are
terminated.
No
Incorrect
communication
configuration:
different baud
rates between bus
devices.
Incorrect
connection:
terminals A and B
are mixed up.
Alarm relays
Relays do not
No alarm message
energise
due to defective
component or
defective controlling
devices. No alarm
source has been
assigned.
Relays do not
No alarm reset
de-energise
due to sticking or
defective relay.
Switching current
> 5 A.
No switching of
the relay due to
excessive preloads
on contacts.
Enclosure
Broken screw-
Device becomes
mounting
detached due to
brackets
broken mounting
brackets.
Non-compliance
Insufficient
with the
insulation due to
insulation
insufficient distance
guideline
between mounting
screws and
connecting wires.
Terminals
Wires detach
Due to splicing
from the
of wire ends, it
terminal
is not possible to
insert them into
the terminal or hold
them firmly in the
terminal.
Wires cannot
Ferrules with strong
be removed
crimp impressions
from terminal
get stuck in the
terminal
Correction
Source
Configure the
terminating resistor,
determine the
terminating resistor
value and replace it if
necessary.
Configure the
terminating resistor,
check quality of the
bus signal.
Calibrate baud rates
between all bus
devices.
Establish correct bus
wiring.
Check relay for proper
function, replace
device if necessary.
Assign alarm sources.
Replace device, if
necessary. Observe
technical data of the
switching output.
Observe technical
data of the switching
output.
Preventive measure:
Use correct screw
type and observe max.
tightening torque. If
the screw-mounting
brackets are defective:
mount on DIN rail or
replace device.
Use screws with
plastic cover or mount
on DIN rail.
Use ferrules for
mounting and
connection to flexible
cables.
Use correct crimping
pliers for mounting
and connection with
flexible cables.