Configuring The Inverter To Work Only With The Pv Array, Without Batteries; Configuring The Soc Settings; Configuring The Maximum Battery Charge Power From The Auxiliary Genset; Configuring The Ac Voltage And Rated Frequency Of The Loads In Stand-Alone Installations - Ingeteam INGECON SUN STORAGE 1Play Installation And Operation Manual

Hide thumbs Also See for INGECON SUN STORAGE 1Play:
Table of Contents

Advertisement

Display control
18.7. Configuring the inverter to work only with the PV array,
without batteries
These inverters can work only from the photovoltaic input, without using the battery input.
INFO
To set up the inverter in this operation mode, see the document "Use and Settings of the ISS 1Play working
only with PV" available at www.ingeconsuntraining.info.

18.8. Configuring the SOC settings

Setting
SOCMAX
SOCRED
SOCMIN
SOCRECX
SOCDESCX
18.9. Configuring the maximum battery charge power from the
auxiliary genset
This option allows to set the maximum power for charging the batteries from the generator.
To configure this parameter, open MAIN MENU > CONFIGURATION > OPERATION MODE > MODE > open the
selected mode> CHARGING POWER and specify the maximum power in watts.
When the inverter is connected to the grid or generator, the batteries are charged from the AC source when the
state of charge (SOC) is lower than the set SOC MIN (see "18.8. Configuring the SOC settings").
18.10. Configuring the AC voltage and rated frequency of the loads
in stand-alone installations
In stand-alone installations these units allow to power the consumption grid with configurable AC voltage and
frequency.
To configure the AC voltage and rated frequency, open the MAIN MENU > CONFIGURATION > INVERTER.
Setting
RMS VOLTAGE
FREQUENCY
18.11. Configuring the auxiliary generator in stand-alone
installations
In stand-alone installations these inverters can operate with an auxiliary generator that is connected in the event of
a power deficit.
To configure the generator settings, open MAIN MENU > CONFIGURATION > GENSET > GRID TYPE >
GENERATOR and enter the generator settings.
Setting
RATED POWER
VAC MIN
ABH2015IQE01_ - Installation and Operation Manual
Maximum state of charge for charging the batteries from the photovoltaic energy (%).
Maximum state of charge for disconnecting the auxiliary generator (%).
Minimum state of charge for starting the auxiliary generator (%).
Reboot state of charge of supply to the consumers using photovoltaic energy (no diesel generator
available) (%).
Minimum state of charge to fully discharge the batteries, stopping the supply to the consumers (%).
Rated voltage supplying the AC consumers (V).
Rated frequency of the consumer output (Hz).
Rated power of the diesel generator set (w). With this parameter, the INGECON SUN
STORAGE 1Play estimates the power available for loading the batteries, considering the
consumption of the installation from the diesel generator.
Minimum AC voltage generated by the diesel generator set (V):
Description
Description
Description