Connecting The Pv Array; Safety Instructions For Connecting The Pv Array; Wiring Requirements For Connecting The Pv Array; Pv Array Connection Process - Ingeteam INGECON SUN STORAGE 1Play Installation And Operation Manual

Hide thumbs Also See for INGECON SUN STORAGE 1Play:
Table of Contents

Advertisement

Ingeteam

11. Connecting the PV array

These units can be connected to a PV array.
This chapter explains the requirements and process for connecting the PV array wiring to the unit. Read carefully
before starting the connection process.
CAUTION
The PV array cannot be grounded, so its terminals must be isolated from ground.
INFO
The inverter will only start if the ground impedance of the PV array is higher than 18.3 kOhms.

11.1. Safety instructions for connecting the PV array

CAUTION
Before you start to make the connections, make sure there is no voltage in the inverter. Verify that the AC
protection of the auxiliary genset and the DC protection of the storage system are open, as well as the PV array
and the consumption grid.
Do not switch on the power to the unit until you have successfully made the rest of the connections and the unit
is closed.
When carrying out the connections, respect the polarities marked on the unit.
Ingeteam accepts no liability for any damages caused by an incorrect connection.

11.2. Wiring requirements for connecting the PV array

The wiring gauge for connecting the PV array is specified in the following table:
Wiring gauge
Connector type

11.3. PV array connection process

To carry out the connection of the PV array, follow the steps below:
1.
Ensure that the DC switch for the PV array, which is located in the lower part of the unit, is OFF.
34
INGECON SUN STORAGE 1Play
4 ~ 6 mm
2
MC4
DC switch for the PV array
ABH2015IQE01_ - Installation and Operation Manual
Connecting the PV array

Advertisement

Table of Contents
loading

Table of Contents