Ingeteam INGECON SUN STORAGE 1Play Installation And Operation Manual page 60

Hide thumbs Also See for INGECON SUN STORAGE 1Play:
Table of Contents

Advertisement

Ingeteam
These inverters can work with lead-acid batteries and with Li-Ion batteries.
To select the desired battery type, open MAIN MENU > CONFIGURATION > BATTERY.
The > symbol points to the type of battery currently selected. To select a different battery, highlight it using the UP
or DOWN keys and press OK.
Lead-Acid batteries
For the lead-acid batteries to work properly and to safely prevent overcharges and complete discharges,
several settings related to the battery model installed must be configured. To do this, open MAIN MENU >
CONFIGURATION > BATTERY > LEAD-ACID > SETTINGS.
CAUTION
An incorrect configuration of these settings can reduce the battery life. Ingeteam accepts no liability for the
consequences that may arise from incorrect configuration of the unit by the user and/or the installer.
Setting
RATED V
MINIMUM V
CAPACITY 20H
CAPACITY 5H
I CHARGE
I DISCHARGE
V ABSORPTION
V FLOTATION
V EQUALIZATION
T EQUALIZATION
In addition, to prevent overcharging and incomplete charging of the lead-acid batteries, these inverters allow to
constantly monitor the battery temperature through a PT100 sensor. This allows to adapt the charge voltage to the
current temperature of the battery at any time.
To activate the automatic temperature compensation, open MAIN MENU > CONFIGURATION > BATTERY > LEAD-
ACID > PT100 BATTERY SENSOR.
At temperatures equal to or higher than 20 ºC the inverter reduces the battery charge voltage. At temperatures
below 20 ºC the inverter increases the battery charge voltage. To modify the compensation constant in V/ºC/Cell,
open MAIN MENU > CONFIGURATION > BATTERY > LEAD-ACID > SETTINGS.
Setting
COMP. TEMP.
Li-Ion batteries
The Li-Ion batteries suitable for the INGECON SUN STORAGE 1Play have their own advanced battery
management, which is usually programmed by the manufacturer and integrated in the batteries (BMS). Ingeteam
cannot in any way change the operation of this external advanced battery management.
INFO
For more information about the compatible Li-Ion batteries, see the "List of Li-Ion batteries approved for the
INGECON SUN STORAGE 1Play" available on the Ingeteam website.
If the battery model is not in the list, contact Ingeteam.
60
Rated voltage of the battery bank (V).
Minimum voltage of the battery bank to avoid complete discharges, even stopping the supply
from the batteries to the consumers (V).
C20 capacity specified by the battery manufacturer (Ah). This setting is used to precisely
determine the battery state of charge (SOC).
C5 capacity specified by the battery manufacturer (Ah). This setting is used to precisely
determine the battery state of charge (SOC).
Maximum charge current of the battery bank (A).
Maximum discharge current of the battery bank (A).
Absorption voltage of the battery bank (V).
Flotation voltage of the battery bank (V).
Equalization voltage of the battery bank (V).
Duration of equalization charge. Time for which the battery bank must be maintained at the
equalization voltage (minutes).
Compensation temperature in a cell, in –mV/ºC/Cell. See the battery datasheet. The default
value is -4mV/ºC/Cell.
Description
Description
ABH2015IQE01_ - Installation and Operation Manual
Display control

Advertisement

Table of Contents
loading

Table of Contents