INGECON SUN STORAGE 1PLAY
Use and Settings of the ISS 1Play working with PYLONTECH
FORCE H1/H2 and POWERCUBE X1/X2
Ingeteam Power Technology S. A.
Technical Guide

Advertisement

Table of Contents
loading

Summary of Contents for Ingeteam 1PLAY

  • Page 1 INGECON SUN STORAGE 1PLAY Use and Settings of the ISS 1Play working with PYLONTECH FORCE H1/H2 and POWERCUBE X1/X2 Ingeteam Power Technology S. A. Technical Guide...
  • Page 2: Table Of Contents

    Black start function ............................5 Battery´s firmware update ..........................6 Setting the inverter ............................7 DC Battery type ........................... 7 5.1.1 For ISS 1Play TL M ......................... 7 5.1.2 For ISS 1Play TL ..........................7 Final check ..............................9 Trouble shooting ............................10...
  • Page 3: Introduction

    INGECON SUN STORAGE 1Play 1 Introduction This document describes the process to configure the INGECON SUN STORAGE 1Play (TL and TL M version) to work with PYLONTECH FORCE H1/H2 and POWERCUBE X1/X2 batteries. The PYLONTECH HV and ISS 1Play equipment can be used in the following type of single-phase installations: •...
  • Page 4: Connecting The Battery Pack To The Inverter

    When the battery does not receive for 15 seconds such a command, its internal circuit breaker opens. The ISS 1Play uses a two-pin CAN terminal and the Pylontech uses a RJ45 connector. For further details, check the “Installation and Operation Manual” of ISS 1Play. The pin-out is the following: Only for ISS 1Play TL, it is mandatory that its display is correctly connected.
  • Page 5: Black Start Function

    INGECON SUN STORAGE 1Play 3 Black start function This chapter describes how to turn on the system when the PV energy is not available, and the battery is the only source to turn on the inverter. To do so, once all the previous steps have been completed, the following steps must be followed: 1) Make sure that the battery circuit breaker is in OFF position.
  • Page 6: Battery´s Firmware Update

    RS-232 supplied by the distributor. For further details, check the “Pylontech guideline” supplied by the distributor. A minimum firmware version is necessary to work with the Ingecon Sun Storage 1Play: • Force H1/H2 → V1.3 or higher •...
  • Page 7: Setting The Inverter

    INGECON SUN STORAGE 1Play 5 Setting the inverter This chapter describes how to configure the inverter settings when the ISS 1Play has been wired to the Pylontech battery. To do so, once all the previous steps have been completed, the following steps must be followed: 5.1 DC Battery type...
  • Page 8 INGECON SUN STORAGE 1Play The password is indicated on the “Installation and Operation Manual”, on the chapter dedicated to configuration. When the permission is given, go to: MAIN MENU > CONFIGURATION > BATTERY > LITHIUM > PYLONTECH HV > FORCE H1/H2 MAIN MENU >...
  • Page 9: Final Check

    INGECON SUN STORAGE 1Play 6 Final check This chapter describes the instructions to check that all the connections and settings have been successfully done. 1) Make sure that the CAN communication wire from the PYLONTECH battery to the inverter is connected.
  • Page 10: Trouble Shooting

    INGECON SUN STORAGE 1Play 7 Trouble shooting The inverter receives battery´s alarms from BMS and reacts different for each alarm. Inverter notifies via Interface Web when battery is in alarm status: Also, the inverter shows the alarm: The reaction of the inverter for each alarm is:...
  • Page 11 INGECON SUN STORAGE 1Play CUT: Charge Cell Under Temperature In on-grid, stop battery Protect 0x0010 charge & discharge. Low Temperature DUT: Discharge Cell Under Temperature In off-grid, stop inverter Protect Bit 7: Other Error Bit 6: Other Error Bit 5: Relay Check Error...