Configuring The Digital Outputs; Configuring The Digital Inputs - Ingeteam INGECON SUN STORAGE 1Play Installation And Operation Manual

Hide thumbs Also See for INGECON SUN STORAGE 1Play:
Table of Contents

Advertisement

Ingeteam
Setting
VAC MAX
FAC MIN
FAC MAX
The generator can start automatically using a command through a digital output in the inverter. For this, the digital
output must be configured as "Generator ON/OFF" (see "18.12. Configuring the digital outputs"). The options
available for starting the auxiliary generator through the inverter are:
Options
Battery state of charge (SOC)
Scheduling
Consumption grid overload
Manual

18.12. Configuring the digital outputs

These inverters have several voltage-free outputs which can have the following functionalities:
Options
NO CONFIGURATION
GENERATOR ON/OFF
LOW BAT. VOLTAGE
HIGH BAT. VOLTAGE
NEUTRAL GROUND
ON/OFF BY COM.
To configure the digital outputs, open MAIN MENU > CONFIGURATION > DIGITAL I/O.

18.13. Configuring the digital inputs

These inverters have several digital inputs which can have the following functionalities:
Options
NO CONFIGURATION
INVERTER START/STOP
To configure the digital outputs, open MAIN MENU > CONFIGURATION > DIGITAL I/O.
62
Maximum AC voltage generated by the diesel generator set (V):
Minimum frequency generated by the diesel generator set (Hz):
Maximum frequency generated by the diesel generator set (Hz):
This allows the generator to be switched on once the state of charge reaches the SOC MIN
parameter and, if the batteries are lead-acid, when the battery reaches the V MIN parameter.
The generator is switched off once the state of charge reaches the SOC RED parameter. This
option is always activated by default and cannot be deactivated.
When this function is activated, the generator will be switched on/off every day during a range
of defined hours.
When this function is activated, the generator is switched on/off according to the power
consumed by the loads in a set time.
This allows you to switch the generator on/off manually and immediately. The generator will
continue to run until the shut-down is ordered by the same method.
Description
No task assigned (default option)
Auxiliary generator activation signal
Signal used to indicate that the battery voltage is
lower than the minimum voltage configured. After
selecting this option the minimum voltage must be
set.
Signal used to indicate that the battery voltage is
higher than the maximum voltage configured. After
selecting this option the maximum voltage must
be set.
Neutral grounding of the consumers using a
normally open external contactor. In the event of
a TT (Off-grid) grid outage, the contactor will be
activated.
Digital output control via communications.
Description
No task assigned (default option)
Starts or stops the inverter
Description
Description
State of the normally open (NO) voltage-
free contact
OPEN
Turn off the generator: OPEN
Turn on the generator: CLOSED
Voltage above the limit: OPEN
Voltage below the limit: CLOSED
Voltage above the limit: OPEN
Voltage below the limit: CLOSED
TT neutral to ground in On-grid: OPEN
TT neutral to ground in Off-grid: CLOSED
Off: OPEN
On: CLOSED
State of the voltage-free contactor /
Voltage level
OPEN / High level
Start: OPEN / High level
Stop: CLOSED / Low level
ABH2015IQE01_ - Installation and Operation Manual