Connecting the storage system temperature sensor
12.3. Storage system temperature sensor connection process
To connect the temperature sensor:
1.
Loosen the corresponding packing gland (see Section "2.7. Description of cable inlets"), remove the cap
and pass the sensor cable through it.
2.
Connect the wiring to terminal J76 PT-100 BAT, as indicated in the above figure, respecting the wiring
colors. The colors of the wires to connect to each terminal appear on the screen-printed electronic card
(R: red, R: red, W: white).
3.
Correctly tighten the packing glands to prevent losses to the protection class, verifying that the wiring is
not taut. Check that the connection is tight.
ABH2015IQE01_ - Installation and Operation Manual