Connecting The Battery Pack To The Inverter; Wiring Of Can Communication Wire - Ingeteam 1PLAY Quick Start Manual

Ingecon sun storage
Table of Contents

Advertisement

2 Connecting the battery pack to the inverter

The instructions to connect the battery pack to the inverter are described in the "Installation Manual of
Pylontech"
Please, take into account the following technical notes:
1) The inverter is turned OFF before connecting the battery pack to the inverter.
2) The battery circuit breaker is on the OFF position.
3) Connect the DC power wires with 6-10mm
4) Connect the CAN Communication wire.

2.1 Wiring of CAN communication wire

Pylontech batteries require a CAN communication wire to the ISS 1Play.
The ISS 1Play will send the necessary keep-a-live command to the Pylontech battery, which is needed to
keep its internal circuit breaker close. When the battery does not receive for 15 seconds such a command, its
internal circuit breaker opens.
The ISS 1Play uses a two-pin CAN terminal and the Pylontech uses a RJ45 connector. For further details,
check the "Installation and Operation Manual" of ISS 1Play. The pin-out is the following:
Only for ISS 1Play TL, it is mandatory that its display is correctly connected. Otherwise, the Pylontech will
open its internal circuit breaker after 15 seconds.
Technical Guide
2
.
19/11/2020
INGECON SUN STORAGE 1Play
4/11

Advertisement