Connecting optional accessories

16. Connecting optional accessories
This chapter explains the process for wiring the optional accessories to the unit:
Communication card.
INGECON SUN EMS Board energy manager.

16.1. Safety instructions for connecting the optional accessories

CAUTION
Before you start to make the connections, make sure there is no voltage in the inverter. Verify that the AC
protection of the auxiliary genset and the DC protection of the storage system are open, as well as the PV array
and the consumption grid.
Do not switch on the power to the unit until you have successfully made the rest of the connections and the unit
is closed.

16.2. Connecting the communication cards

Optionally, it is possible to install the cards required to establish communication with the inverter. There are
several ways establish communication:
RS-485.
Ethernet TCP.
Wi-Fi TCP.
INFO
See the corresponding communication accessories manual for further information.

16.2.1. RS-485 communication card

The RS-485 communication card is installed inside the unit. Follow the steps below to connect the
communications card:
1.
Connect the communication card in the J11 and J12 connectors of the control card.
2.
Insert the wiring to the unit through the cable inlets provided in the lower part of the inverter (see "2.7.
Description of cable inlets").
ABH2015IQE01_ - Installation and Operation Manual
J11
J12
Ingeteam
45