3 Connecting the battery pack to the inverter
The instructions to connect the battery pack to the inverter are described in the "Installation Manual of LG
RESU 3.3 / 6.5 /10"
Please, take into account the following technical notes:
•
The inverter is turned OFF before connecting the battery pack to the inverter.
•
The battery circuit breaker is on the OFF position.
•
Do NOT connect any ground wire (PE) between the battery pack and the inverter. The battery pack
must be isolated from the floor, for example with a wood panel. The ground wire (PE) is only
connected between AC Grid and Inverter.
•
2
Use 10-16 mm
"Installation and Operation Manual" from the ISS 1Play.
3.1 Wiring of communication cable
LG Chem RESU batteries require a communication wire to the ISS 1Play.
The ISS 1Play will send the necessary keep-a-live command to the LG RESU battery, which is needed to
keep its internal circuit breaker close. When the battery does not receives for 10 minutes such a command, its
internal circuit breaker opens.
The ISS 1Play uses a three-pin CAN BAT connector and the LG RESU uses a RJ-45 connector. The pin-out
is the following:
Pin-out
GND
CAN-L
CAN-H
Technical Guide
for the positive and negative power wires following the indications given in the
ISS 1Play TL M
----
J8 – BMS CAN_L
J8 – BMS CAN_H
22/04/2020
ISS 1Play TL
LG RESU RJ-45
J76 – CAN IN-GND
J76 – CAN IN-L
J76 – CAN IN-H
INGECON SUN STORAGE 1Play
Pin 2
Pin 5
Pin 4
5/10