To mount an expander

WARNING
When you handle the expander:
• Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
• Do not touch components or leads.
• Handle the board by its edges.
• Isolate from high voltage or electrostatic discharge.
• Ensure that you are properly grounded.
Wiring restrictions for connecting the expander to the MPC Open XP
Maximum length: 100 feet (30 meters)
22 or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
You can mount the expander in one of the following locations:
On top of a MPC Open XP, using the two allen cap screws provided. Connect Gnd to Gnd, Xnet- to Xnet-,
Xnet+ to Xnet+.
Beside the MPC Open XP, by screwing the expander into an enclosed panel using the mounting slots on the
coverplate. Leave about 2 in. (5 cm) on each side of the expander for wiring. Mounting hole dimensions 1.5"
from the left (width) by 10.2" (height). Connect Gnd to Gnd, Xnet- to Xnet-, Xnet+ to Xnet+. You can mount the
expander up to 100 ft away from the controller.