Safety Considerations - Carrier i-Vu MPC Open XP IO48/816 Installation And Startup Manual

Table of Contents

Advertisement

Introduction
Protection
Status indicators
Environmental operating
range
Storage temperature range
Physical
Overall dimensions
Mounting dimensions
(in a panel)
Depth
Weight
Listed by

Safety considerations

WARNING Disconnect electrical power to the MPC Open XP before wiring it. Failure to follow this warning
could cause electrical shock, personal injury, or damage to the controller.
MPC Open XP
MPC Open XP IO48/816
Installation and Start-up Guide
Incoming power - 2 replaceable 3 Amp Pico
Power, network, I/O connections - protected against voltage transient and surge
events
LED's indicate status of communications, running, errors, and outputs
-20 to 140°F (-29 to 60°C), 10–90% relative humidity, non-condensing
NOTE Install in a UL Listed enclosure only.
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Rugged aluminum cover, removable screw-type terminal blocks
A:
9 in. (22.9 cm)
B:
4-13/16 in. (12.2 cm)
C:
8-5/8 in. (21.8 cm)
D:
1 in. (2.5 cm)
E:
2-13/16 in (7.1 cm)
F:
1/4 in. (.6 cm)
1-7/16 in. (3.7 cm)
13.3 oz. (.377 kg)
UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-Class A, CE
Carrier Proprietary and Confidential
®
fuses
6