To use the Auto-Off-On switches

You can control an output using the Auto-Off-On switch.
Set the switch to...
On
Off
Auto
The potentiometer, located between the Auto-Off-On switch and the jumper, allows you to manually control the
output level of an analog output. Place the Auto-Off-On switch in the On position, then turn the potentiometer
counterclockwise to reduce the output, or clockwise to increase the output.
WARNING! The output potentiometer is NOT used for binary output channels. For a binary output, turn the
potentiometer clockwise until it stops (maximum output) and leave it in this position. Failure to do so may result in
relay-chattering or failure of the relay to energize when the Auto-Off-On switch is in the On position.

Wiring devices to the MPC Open XP's Rnet port

The Rnet communicates at a rate of 115 kbps.
Carrier wireless sensors
You can wire a Wireless Adapter to MPC Open XP's Rnet port. The Wireless Adapter communicates with up to 15
wireless sensors. When using wireless sensors, the Rnet can have:
Up to 15 wireless and ZS sensors (any combination)
One Wireless Adapter
One Equipment Touch
MPC Open XP
MPC Open XP IO48/816
Installation and Start-up Guide
To...
Turn on the output.
Turn off the output.
Let the control program control the output.