External Functions - Viessmann Vitotronic 200 Installation And Service Instructions For Contractors

Weather-compensated control unit
Table of Contents

Advertisement

Electrical connections
Connecting actuators
Extension connections for heating circuits 2 and 3, each with mixer
Plug
M2/M3
gS
Connections on the 230 V~ PCB
Plug
gS
A1
M
1~
52
Fig. 19
OPEN
CLOSE
Connecting a central fault message facility
Plug
All system faults are transferred.
L
N
50
Fig. 20

External functions

Overview of external functions
Connections on the low voltage PCB
Function
One of the following functions:
External operating program changeover
Mixer OPEN
26
Component
Mixer motor
Component
One of the following functions:
Mixing valve for return temperature control
Mixing valve, heat exchanger set
Rated voltage
230 V~
Rated current
Max. 0.2 (0.1) A~
Runtime
5 to 199 s
Setting runtime
The runtime can be set by means of the following
parameters:
in conjunction with plug
"56" in the "General" group
"0F" in the "DHW" group
in conjunction with plug
"16" in the "Heating circuit..." group
Rated voltage
Rated current
Plug
aVD
A1:
gS
M2/M3:
gS
230 V~
Max. 4(2) A~
Page
.1/
.2
aVD
27