Viessmann Vitotronic 200 Installation And Service Instructions For Contractors page 65

Weather-compensated control unit
Table of Contents

Advertisement

Boiler
(cont.)
13 Shutdown differential
Display
Without
... K
14 Minimum burner runtime
Display
... min
15 Runtime servomotor mod. burner
Display
... s
16 Burner offset with start optimisation
Display
... K
1A Start optimisation
Display
... s
Value
Explanations
13:0
Without shutdown differential
13:2 to
The burner shuts down when the set boiler water tem-
13:20
perature is exceeded.
Shutdown differential adjustable from 2 to 20 K.
Note
Factory setting, according to coding card
Value
Explanations
14:0 to
Minimum burner runtime in minutes
14:15
Minimum runtime adjustable from 0 to 15 min.
Note
Factory setting, according to coding card
!
Value
Explanations
15:5 to
Runtime adjustable from 5 to 199 s.
15:199
Note
Factory setting, according to coding card
Value
Explanations
16:0 to
Burner offset with start optimisation in K (temporary
16:15
reduction of the set boiler water temperature after
burner start)
Offset adjustable from 0 to 15 K.
Note
Factory setting, according to coding card
Value
Explanations
1A:0 to
Duration of start optimisation after burner start adjust-
1A:60
able from 0 to 60 s.
Note
Factory setting, according to coding card