Viessmann Vitotronic 200 Installation And Service Instructions For Contractors page 70

Weather-compensated control unit
Table of Contents

Advertisement

Parameter
DHW
(cont.)
0B Input of the set DHW temperature
Display
At the programming unit of the control unit
At the control unit and the remote control,
heating circuit 1
At the control unit and the remote control,
heating circuit 2 with mixer
At the control unit and the remote control,
heating circuit 3 with mixer
At the programming unit of the control unit
and all installed Vitotrol 300 remote control
units
At remote control, heating circuit 1
At remote control, heating circuit 2 with
mixer
At remote control, heating circuit 3 with
mixer
0C For solar DHW heating: DHW temperature target
Display
40 °C
None
... °C
0D With 2 tank temperature sensors: Tank heating stop point
Display
...
...
0E With 2 tank temperature sensors: Tank heating start point
Display
...
...
70
Value
Explanations
0B:0
0B:1
0B:2
0B:3
0B:4
0B:5
0B:6
0B:7
!
Value
Explanations
0C:40
Set DHW temperature 40 °C.
Reheating is suppressed above the selected set tem-
perature (DHW heating by the boiler only if solar en-
ergy is insufficient).
0C:0 to
No set value 3
0C:9
0C:10 to
Entry of a 2nd set DHW temperature
0C:95
Note parameter "01" setting.
Adjustable from 10 to 95 °C
Value
Explanations
0D:8
Condition: Parameter "00:2" with 2 cylinder tempera-
ture sensors
Cylinder heating stop point at set value x 0.8
0D:2 to
Adjustable from 0.2 to 1
0D:10
1 step
0.1
Value
Explanations
0E:7
Condition: Parameter "00:2" with 2 cylinder tempera-
ture sensors
Cylinder heating stop point at set value x 0.7
0E:1 to
Adjustable from 0.1 to 0.9
0E:9
1 step
0.1