Viessmann Vitotronic 200 Installation And Service Instructions For Contractors page 33

Weather-compensated control unit
Table of Contents

Advertisement

Connecting an AC burner
41
STB
TR
L1
N T1 T2 S3 B4
Fig. 23
A
To the control unit
To the burner
B
Plug terminal designations
L1
Phase via high limit safety cut-out to the burner
PE
Earth conductor to burner
N
Neutral conductor to burner
T1, T2 Control chain
S3
Burner fault terminal
B4
Hours run meter terminal
Signal flow direction:
Control unit
burner
Signal flow direction:
Burner
control unit
Plug equipment codes
fA
STB Control unit high limit safety cut-out
TR
Control unit temperature controller
H1
Burner fault signal
BZ
Hours run meter
Viessmann matrix burner for Vitocrossal
The burner cables are included in the standard boiler
delivery.
Max. power consumption 6 (3) A
(cont.)
:
fA
:
90
BN
BK
BU
Fig. 24
To the control unit
A
To the burner
B
Plug terminal designations
T6, T8 Control chain burner stage 2 ON or modulation
controller Open
T6, T7 Control chain burner stage 2 OFF or modula-
tion controller Close
Signal flow direction:
Control unit
burner
Signal flow direction:
Burner
control unit
Colour coding to IEC 60757:
BK Black
BN Brown
BU Blue
Burner without plug
Fit the mating plug from Viessmann or from the burner
manufacturer. Connect the burner cable.
Electrical connections
:
33