Troubleshooting
Fault messages
(cont.)
CB Fault message module 1, input 4: Max. pressure 2
Boiler cools down.
Cause
Fault in additional high limit safety cut-out or tempera-
ture limiter at "X1" of plug-in adaptor 1 for external
safety equipment
CE Communication error, fault message module 1
Control mode
Cause
Communication error, plug-in adaptor 1 for external
safety equipment
CF Communication error, LON communication module
Control mode
No communication via LON
Cause
Communication error, LON communication module of
the control unit
D1 Burner fault, boiler
Boiler cools down.
Cause
Burner fault, boiler
D2 Communication error, fault message module 2
Control mode
Cause
Communication error, plug-in adaptor 2 for external
safety equipment
D3 Communication error, EA1 extension
Control mode
104
Measure
Check the system temperature.
Resetting the high limit safety cut-out: See chapter
"Plug-in adaptor for external safety equipment"
Measure
Checking the plug-in adaptor: See chapter "Plug-in
adaptor for external safety equipment"
Without plug-in adaptor: Set parameter "14:0" in the
"General" group.
Measure
Check LON communication module and replace if re-
quired.
If no LON communication module is installed, set pa-
rameter "76:0" in the "General" group.
Measure
Check the burner.
Measure
Checking the plug-in adaptor: See chapter "Plug-in
adaptor for external safety equipment"
Without plug-in adaptor:
Set parameter "15" in the "General" group.