Viessmann Vitotronic 200 Installation And Service Instructions For Contractors page 79

Weather-compensated control unit
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
05 Heating limit: Economy function: Outside temperature
Display
See service instructions
Without
See service instructions
06 Heating limit: Complete summer economy control
Display
None
Function active
07 Mixer economy function
Display
Without
With
Value
Explanations
05:5
Economy function, outside temperature: Heating cir-
cuit pump OFF when the outside temperature (OT) is
1 K higher than the set room temperature (RT
OT
05:0
Without economy function outside temperature
With economy function, outside temperature:
Heating circuit pump OFF
05:1
OT
05:2
OT
05:3
OT
05:4
OT
05:5
OT
05:6
OT
05:7
OT
to
to
05:15
OT
Value
Explanations
06:36
Extended economy function disabled
06:5 to
Extended economy function enabled: The burner and
06:35
heating circuit pump are switched off at a variable val-
ue, adjustable from 5 to 35 °C plus 1 °C. Mixer will be
closed.
The basis for this is the adjusted outside temperature.
This is composed of the actual outside temperature
and a time constant that takes account of the way an
average building cools down.
!
Value
Explanations
07:0
07:1
Heating circuit pump also OFF:
Heating circuit pump ON:
(cont.)
!
RT
+ 1 K
>
set
RT
+ 5 K
>
set
RT
+ 4 K
>
set
RT
+ 3 K
>
set
RT
+ 2 K
>
set
RT
+ 1 K
>
set
RT
>
set
RT
1 K
>
set
RT
9 K
>
set
!
If the mixer has been trying to close for longer than
approximately 12 min.
If the mixer changes to control function
If there is a risk of frost
Parameter
)
set