Viessmann Vitotronic 200 Installation And Service Instructions For Contractors page 68

Weather-compensated control unit
Table of Contents

Advertisement

Parameter
DHW
Note
Parameter values in bold are factory settings.
00 Tank heating
!
Display
Hysteresis
2.5 K
±
Adaptive tank heating enabled
Tank temperature control with 2 tempera-
ture sensors
Tank temperature control, tank loading sys-
tem
01 Selection of set DHW temperature
Display
10 °C .. 60 °C
10 °C .. programmed maximum value
03 Additional function for increased DHW heating
Display
No 2nd set cylinder temperature
No 2nd set cylinder temperature
... °C
04 Cylinder heating: Set start point
Display
2.5 K below set value
... K below set value
68
Value
Explanations
00:0
See chapter "Function description"
00:1
00:2
00:3
Value
Explanations
01:0
Set DHW temperature adjustable from 10 to 60 °C
01:1
Adjustable from 10 to 95 °C
Note
Observe the maximum permissible DHW temperature.
Value
Explanations
03:0
Additional function cannot be enabled.
03:0 to
Additional function cannot be enabled.
03:9
03:10 to
Entry of a 2nd set cylinder temperature
03:95
Adjustable from 10 to 95 °C
Note parameter "01" setting.
Enable additional function by setting the 4th time
phase in DHW time program.
Note
A start and stop time must be set for time phases 2
and 3. These may also be within time phase 1.
Value
Explanations
04:0
Set start point
Set stop point +2.5 K
04:1 to
Adjustable from 1 to 10 K below set value
04:10
2.5 K