Viessmann Vitotronic 200 Installation And Service Instructions For Contractors page 51

Weather-compensated control unit
Table of Contents

Advertisement

General
(cont.)
07 Assigning external input mixer CLOSE to heating circuit
Display
None
Mixer CLOSE, HC 1
Mixer CLOSE, HC 2
Mixer CLOSE, HC 1 and HC 2
Mixer CLOSE, HC 3
Mixer CLOSE, HC 1 and HC 3
Mixer CLOSE, HC 2 and HC 3
Mixer CLOSE, HC 1, HC 2 and HC 3
External blocking
External blocking and mixer CLOSE, HC 1
External blocking and mixer CLOSE, HC 2
External blocking and mixer CLOSE, HC 1
and HC 2
External blocking and mixer CLOSE, HC 3
External blocking and mixer CLOSE, HC 1
and HC 3
External blocking and mixer CLOSE, HC 2
and HC 3
External blocking and mixer CLOSE, HC 1,
HC 2 and HC 3
08 Assigning operating mode changeover to heating circuit
Display
None
Heating circuit 1
Heating circuit 2
Heating circuit 1 and heating circuit 2
Heating circuit 3
Heating circuit 1 and heating circuit 3
Heating circuit 2 and heating circuit 3
Heating circuit 1, heating circuit 2 and heat-
ing circuit 3
Value
Explanations
07:0
Connection at terminals 2 and 3 in plug 143 inactive
07:1
07:2
07:3
07:4
07:5
07:6
07:7
07:8
07:9
07:10
07:11
07:12
07:13
07:14
07:15
Value
Explanations
08:0
Connection at terminals 1 and 2 in plug 143 inactive
(External operating program changeover)
08:1
Contact affects the following heating circuits:
Heating circuit 1 without mixer
08:2
Heating circuit 2 with mixer
08:3
Heating circuit 1 without mixer and heating circuit 2
with mixer
08:4
Heating circuit 3 with mixer
08:5
Heating circuit 1 without mixer and heating circuit 3
with mixer
08:6
Heating circuit 2 and heating circuit 3 with mixer
08:7
Heating circuit 1 without mixer, heating circuit 2 and
heating circuit 3 with mixer
Parameter
51

Advertisement

Table of Contents
loading

This manual is also suitable for:

Co1e

Table of Contents