Viessmann Vitotronic 200 Installation And Service Instructions For Contractors page 82

Weather-compensated control unit
Table of Contents

Advertisement

Parameter
Heating circuit 1, heating circuit 2, heating...
12 Learning start optimisation
Display
Without
With
13 Shutdown time optimisation
Display
Without
With stop optimisation, max. setback time
offset 1 h
With stop optimisation, max. setback time
offset 2 h
14 Stop optimisation of setback time offset
Display
Without
... min
15 Learning shut-down time optimisation
Display
Without
With
16 Mixer runtime
Display
125 s
... s
82
(cont.)
Value
Explanations
12:0
With remote control and for the heating circuit, opera-
tion with room temperature hook-up must be program-
med: Without learning start optimisation
12:1
Value
Explanations
13:0
With remote control and for the heating circuit, opera-
tion with room temperature hook-up must be program-
med: Without stop optimisation
13:1
13:2
Value
Explanations
14:0
With remote control and for the heating circuit, opera-
tion with room temperature hook-up must be program-
med: Stop optimisation of setback time offset
14:1 to
With stop optimisation of setback time offset
14:12
Adjustable from 10 to 120 min
1 step ≙ 10 min
Value
Explanations
15:0
With remote control and for the heating circuit, opera-
tion with room temperature hook-up must be program-
med: Without learning stop optimisation
15:1
With learning shut-down time optimisation
Value
Explanations
16:125
For heating circuits with mixer only: Mixer runtime
125 s
16:10 to
Adjustable from 10 to 255 s
16:255