Parameter
Heating circuit 1, heating circuit 2, heating...
12 Learning start optimisation
Display
Without
With
13 Shutdown time optimisation
Display
Without
With stop optimisation, max. setback time
offset 1 h
With stop optimisation, max. setback time
offset 2 h
14 Stop optimisation of setback time offset
Display
Without
... min
15 Learning shut-down time optimisation
Display
Without
With
16 Mixer runtime
Display
125 s
... s
82
(cont.)
Value
Explanations
12:0
With remote control and for the heating circuit, opera-
tion with room temperature hook-up must be program-
med: Without learning start optimisation
12:1
Value
Explanations
13:0
With remote control and for the heating circuit, opera-
tion with room temperature hook-up must be program-
med: Without stop optimisation
13:1
13:2
Value
Explanations
14:0
With remote control and for the heating circuit, opera-
tion with room temperature hook-up must be program-
med: Stop optimisation of setback time offset
14:1 to
With stop optimisation of setback time offset
14:12
Adjustable from 10 to 120 min
1 step ≙ 10 min
Value
Explanations
15:0
With remote control and for the heating circuit, opera-
tion with room temperature hook-up must be program-
med: Without learning stop optimisation
15:1
With learning shut-down time optimisation
Value
Explanations
16:125
For heating circuits with mixer only: Mixer runtime
125 s
16:10 to
Adjustable from 10 to 255 s
16:255