Viessmann Vitotronic 200 Installation And Service Instructions For Contractors page 63

Weather-compensated control unit
Table of Contents

Advertisement

Boiler
Note
Parameter values in bold are factory settings.
02 Burner type
!
Display
Single stage burner
Two-stage burner
Modulating burner
03 Boiler protection, gas/oil operation
Display
Gas operation
Oil operation
Resetting to gas not possible.
04 Switching hysteresis burner
Display
Switching hysteresis 4 K
ERB50 function
ERB80 function
05 Burner curve
!
Display
Linear burner curve
% of rated output at 1/3 of the modulation
range
06 Maximum boiler water temperature limit
Display
... °C
Value
Explanations
02:0
02:1
02:2
!
Value
Explanations
03:0
03:1
Value
Explanations
04:0
Note
Factory setting, according to coding card
04:1
Only for single stage burner
04:2
Value
Explanations
05:0
Note
Factory setting, according to coding card
05:1 to
05:99
The burner curve varies depending on the type of
burner.
The burner curve shows the burner output (in %) in re-
lation to the opening angle of the butterfly valve (in
%).
See chapter "Matching the control unit to the modulat-
ing burner".
!
Value
Explanations
06:20 to
See chapter "Function description"
06:127
Note
Factory setting, according to coding card
Observe the temperature controller settings.
Parameter
63