Connecting pumps
Pumps in the underfloor heating circuit
M
1~
B
A
Fig. 17
Control unit
Primary heating circuit pump
A
Temperature limiter
B
Secondary heating circuit pump
C
(for system separation)
Temperature limiter for maximum temperature limiter (accessories)
C
B
M
A
1~
Fig. 18
A
Heating circuit pump
Temperature controller/temperature limiter
B
Plug
of the temperature controller/temperature
C
limiter to the control unit
(cont.)
M
1~
C
The common power consumption of both pumps must
not exceed 2 A.
Electromechanical temperature limiter according to the
liquid expansion principle
Switches the heating circuit pump off when the set
value has been exceeded.
The flow temperature is only slowly reduced in this
situation, i.e. it may be several hours before the sys-
tem restarts again automatically.
Connection: Screw terminals for 1.5 mm
Specification
Setting range
Switching differential
Immersion thermostat
Contact thermostat
Electrical connections
2
30 to 80 °C
Max. 11 K
Max. 14 K