Viessmann Vitotronic 200 Installation And Service Instructions For Contractors page 78

Weather-compensated control unit
Table of Contents

Advertisement

Parameter
Heating circuit 1, heating circuit 2, heating...
03 Temperature limits, frost protection function
Display
2 °C
9 °C
8 °C
7 °C
6 °C
5 °C
4 °C
3 °C
2 °C
1 °C
0 °C
1 °C
2 °C
to
15 °C
04 Frost protection
Display
With
Without
78
(cont.)
Value
Explanations
03:2
Outside temperature below 1 °C: Heating circuit pump
ON
Outside temperature above 3 °C: Heating circuit
pump OFF
!
Please note
If a value below 1 °C is selected, pipes outside
the thermal envelope of the building could
freeze up.
Use settings below 1 °C only if pipes are equip-
ped with appropriate thermal insulation.
Heating circuit pump
ON
03:-9
10 °C
03:-8
9 °C
03:-7
8 °C
03:-6
7 °C
03:-5
6 °C
03:-4
5 °C
03:-3
4 °C
03:-2
3 °C
03:-1
2 °C
03:0
1 °C
03:1
0 °C
03:2
1 °C
to
to
03:15
14 °C
Value
Explanations
04:0
Frost protection enabled
04:1
No frost protection.
Can only be adjusted if parameter "03:-9" has been
set.
OFF
8 °C
7 °C
6 °C
5 °C
4 °C
3 °C
2 °C
1 °C
0 °C
1 °C
2 °C
3 °C
to
16 °C