Weather-compensated control unit
Table of Contents

Advertisement

External functions
(cont.)
External mixer CLOSE/mixer OPEN
!
Please note
Live contacts lead to short circuits or phase fail-
ure.
The external connection must be potential-
free.
External mixer CLOSE/mixer OPEN via switching contacts
Function
Mixer CLOSE
Connection
Plug
1
143
B
A
B
Contact
Closed
Programmed mixers are closed.
Open
Programmed mixers are in control mode.
Parameter
With parameter "07" in the "General"
group assign the function to the heating cir-
cuits.
External changeover of multi stage/modulating burners
!
Please note
Live contacts lead to short circuits or phase fail-
ure.
The external connection must be potential-
free.
Function
External changeover, stepped / modulating burner
Connection
aVH
1
146
A
.2/
.3
aVD
aVD
A
2 3
Floating contact
Plug
of the control unit
aVD
.1/
.2
aVH
A
2 3
Floating contact
Electrical connections
Mixer OPEN
Plug
.1/
.2
aVD
aVD
A
1
2 3
143
B
Floating contact
A
To the control unit
B
Programmed mixers are in control mode.
Programmed mixers are closed.
With parameter "0A" in the "General"
group, assign the function to the heating cir-
cuits.
29