Viessmann Vitotronic 200 Installation And Service Instructions For Contractors page 34

Weather-compensated control unit
Table of Contents

Advertisement

Electrical connections
Connecting an AC burner
A
B4 S3 T2 T1 N
L
41
B
Fig. 25
To the control unit
A
To the burner
B
Plug terminal designations
L1
Phase via high limit safety cut-out to the burner
PE
Earth conductor to burner
N
Neutral conductor to burner
T1, T2 Control chain
S3
Burner fault terminal
B4
Hours run meter terminal
Signal flow direction:
Control unit
burner
Signal flow direction:
Burner
control unit
34
(cont.)
:
fA
A
BN
BK
BU
BN
BK
BU
90
T6
T7T8
B
Fig. 26
To the control unit
A
To the burner
B
Terminal designations:
T6, T8 Control chain burner stage 2 ON or modulation
controller Open
T6, T7 Control chain burner stage 2 OFF or modula-
tion controller Close
Colour coding to IEC 60757:
BK Black
BN Brown
BU Blue

Advertisement

Table of Contents
loading

This manual is also suitable for:

Co1e

Table of Contents