Viessmann Vitotronic 200 Installation And Service Instructions For Contractors page 73

Weather-compensated control unit
Table of Contents

Advertisement

Solar
(cont.)
05 Min. speed, solar circuit pump
Display
10 %
... %
06 Max. speed, solar circuit pump
Display
75 %
... %
07 Interval function, solar circuit pump
Display
OFF
ON
08 Maximum cylinder temperature
Display
60 °C
... °C
09 Maximum collector temperature
Display
130 °C
... °C
0A Stagnation time reduction
Display
None
5 K
... K
Value
Explanations
05:10
Min. speed of the solar circuit pump 10 % of max.
speed
05:2 to
Minimum speed of the solar circuit pump adjustable
05:100
from 2 to 100 %
Value
Explanations
06:75
Maximum speed of solar circuit pump 75 % of max.
speed
06:2 to
Maximum speed of solar circuit pump adjustable from
06:100
2 to 100 %
Value
Explanations
07:0
Interval function of solar circuit pump switched off
07:1
To capture the collector temperature more accurately,
the solar circuit pump periodically starts for a short du-
ration.
Value
Explanations
08:60
Set DHW temperature (maximum cylinder tempera-
ture) 60 °C
08:10 to
Set DHW temperature adjustable from 10 to 90 °C
08:90
Value
Explanations
09:130
Maximum collector temperature (to protect system
components) 130 °C
09:20 to
Maximum collector temperature adjustable from 20 to
09:200
200 °C
Value
Explanations
0A:0
Stagnation time reduction not active
0A:5
Temperature differential for stagnation time reduction
5 K
Reduction in the speed of the solar circuit pump to
protect system components and heat transfer medi-
um.
0A:1 to
Temperature differential adjustable from 1 to 40 K
0A:40
Parameter