Parameter
General
(cont.)
54 Connection at plug 29
Display
Distribution pump
Shunt pump
Boiler circuit pump
Boiler circuit pump with butterfly valve func-
tion
55 Connection at plug 52
Display
Butterfly valve
Mixing valve for return temperature control
Mixing valve, heat exchanger set
Do not adjust
56 Runtime, servomotor, butterfly valve/return temperature control
Display
125 s
... s
57 Run-on time, shunt pump, boiler circuit pump or distribution pump
Display
5 min
None
... min
62 Central control of heating circuits
Display
None
Heating circuit 1
Heating circuit 2
Heating circuit 3
58
Value
Explanations
54:0
Do not adjust
54:1
Note
Factory setting, according to coding card
54:2
54:3
Value
Explanations
Note
Factory setting, according to coding card
55:0
Do not adjust
55:1
55:2
55:3
Value
Explanations
56:125
56:5 to
Adjustable from 5 to 199 s
56:199
Value
Explanations
57:5
57:0
57:1 to
Run-on time for circulation pump on plug 29
57:60
Adjustable from 1 to 60 min
Note
Connection to distribution pump not possible
Value
Explanations
62:0
Without central control of heating circuits
62:1
With central control of heating circuit 1 without mixer
62:2
Heating circuit 2 with mixer
62:3
Heating circuit 3 with mixer
!