Table of Contents 1.0 Operation and Programming Concepts ................1 1.1 Introduction ........................1 1.2 General Information .......................2 1.3 Networks ........................2 1.4 Addressable Devices .....................5 1.5 Resetting 4-Wire Detectors ....................8 2.0 Editing MHI Databases .....................10 2.1 Introduction ........................10 2.2 General Comments ......................10 2.3 System Window ......................11 2.4 Switches Window ......................15 2.5 Groups Window ......................17...
Page 4
List of Figures Figure 1 Typical Network Layout ..................2 Figure 2 Single Network Break ................... 4 Figure 3 Panel Removed from Network ................5 Figure 4 Four Wire Device Wiring (Typical) ................ 9 Figure 5 Modul-R System Window ..................11 Figure 6 Switches Window ....................
Page 5
List of Tables Table 1: Automatic Contact ID/SIA Reporting Codes ............67 Table 2: Contact ID Zone Alarm/Restore Event Codes ............68 Table 3: SIA Format Automatic Zone Alarm/Restore Codes ..........69...
Possible settings\methods option (Y/N) UL864 AC Fail 0 to 30 hours 1, 2 or 3 hours Bell Cutoff 0 or 5 to 30 minutes Introduction This chapter provides an overview of the MR-2100/2200’s (hereafter called the MR-2200) features and supported devices.
Networks 1.3.1 General The MR-2200 can be incorporated into a network including other MR-2900 panels and MR- 2944 annunciators. Though up to 254 panels and annunciators can be supported by the network, such a network would probably be too large to properly maintain. The network can be setup for single building or multiple building operation.
Page 9
Operation and Programming Concepts The basic layout of the network is a single loop (see Figure 1). Each panel and annunciator has a unique ID. There is no requirement that the IDs be sequential or that they start with 1. The master panel can be any fire panel in the network.
Operation and Programming Concepts Network Reboot If a Network Reboot command is initiated at a panel, it is broadcast normally and then the panel reboots itself. Upon receiving the Network Reboot command, a panel passes the command on to the next panel and then reboots itself. This has the affect of causing all the panels to reboot simultaneously.
C O M 2 Figure 3 Panel Removed from Network Addressable Devices 1.4.1 Supported Devices The MR-2200 can use analog/addressable devices. There are two general types of devices: sensors and modules. The following devices are supported: MRI-M500DM Dual Input Monitor Module MRI-M500M...
Page 12
Operation and Programming Concepts MRI-1251 Ionization type smoke detector, low profile MRI-1551 Ionization type smoke detector MRI-2251 Photoelectric type smoke detector, low profile MRI-2551 Photoelectric type smoke detector Photoelectric type smoke detector c/w heat detector, MRI-2251T low profile MRI-2551TH Photoelectric type smoke detector c/w heat detector MRI-2251TMB Acclimate Photo-Thermal Detector MRI-5251...
Page 13
The sensor LED activates the relay and sounder bases. When this LED stays on for more than 10 seconds, the base activates. This requires that the MR-2200 have the LED mode set to FLASH/ON. This is done through the LCD Menu by choosing PROGRAM/ADDRESSABLE/ LED MODE/FLASH.
• Duplicate (D): This means that two devices are using the same address. The MR-2200 does a check every hour for duplicate devices. If either device goes into alarm, the panel operates normally. Note: Due to the method used to detect duplicate devices, it is possible for a single device to appear as duplicate devices.
Editing MHI Databases Editing MHI Databases Introduction This chapter describes the windows used to program the system. General Comments Overview The editing of a system is done through a series of input windows. Editing starts with the System Level and progresses to the Panel Level, then to the Input Level, and finally to the Relate Level.
• MR-2200 Fire Panel: The MR-2200 has two (Class A or B) SLCs and two (expandable to eight) NACs. The NACs can be programmed to be used as either bells or strobe type circuits. The MR-2614 Annunciator can be attached to the MR-2200 panel. It is considered an extension of the panel by MHI and does not change how the panel interfaces with other annunciators.
Page 18
Editing MHI Databases The text in the top left corner provides information about the database. The top line gives the date and time the database was last edited. The next line states whether the current contents have been verified or not; and whether the database has been compressed or not. The options Bell System, Subsequent Alarm, Resound, Evac and Waterflow all affect how the notification appliance circuits (NAC), hereafter referred to as bells, react to alarm conditions.
Page 19
LCD except in STATUS/ IDENTIFICATION. 2.3.11 System Banner The System Banner is a 20 character message that is used as a banner for the Main Menu of the LCD. The default banner is “Modul-R by Secutron.”...
Page 20
Editing MHI Databases 2.3.12 Enforce Local LED Rules The Enforce Local LED Rules check box forces an LED on an input's panel be related. Normally an LED anywhere in the system is all that is required. Note: The common LEDs of any panel are based upon the zone LEDs that are displayed by the panel, not based upon the inputs to the panel.
Editing MHI Databases • More: Everything Latched • Trouble only: Only trouble conditions will auto restore; Note some troubles require user intervention before the panel can determine if the condition be restored • Supv and Trbl: Supervisory and Trouble conditions will automatically restore. 2.3.19 Pushbuttons The System Window has the following push buttons on the right hand side: •...
Editing MHI Databases Changing a switch manually at one panel causes all panels in the network to change switch state. Figure 6 Switches Window 1.Addressable detectors can only be related to a single switch each. 2.Relays, LEDs and control modules controlled by more than one switch stay on as long as any switch operating them is on.
Editing MHI Databases 2.4.6 Description Description is a 20 character message that describes the Switch usage. This is useful in that the switch now has a description of its usage that is easier to understand when assigning Switches to Hot Keys. 2.4.7 Pushbuttons There are five push buttons on the right side: •...
Page 24
Editing MHI Databases The use of Groups greatly simplifies the changes made to a database as changes are needed by the system. For example, if new door is installed that has to be unlocked during a fire alarm, the control module that unlocks the door is simply added to a Group. This single change is then automatically picked up by any inputs that are related to the Group.
Add Panel: Add another panel to the system. A dialog box will be displayed. The default options are to use the next available panel ID and to select an MR-2100, MR-2200, MR-2900 panel or MR-2944, MR-2934 annunciator. You will also be asked if you want MHI to automatically set the Next ID.
Page 26
Editing MHI Databases • Change ID: Displays a dialog box for changing the ID of the current panel. MHI will automatically change all references to use the new ID. This process could take a long time for a large database. A gauge will be displayed to show the progress of the change. •...
Page 27
Editing MHI Databases The IDs Supervised button displays all possible IDs of the MR-2614 and MR-2644 annunciators (see Figure 9) as well as the MR-2801B-MR and MRDL. Check the IDs that will be connected to the system. When the MRDL is enabled, a button will appear next to that option called Dialer Settings (see the section on Dialer Options for a description of the dialer options).
Page 28
Editing MHI Databases Interpreting Flashing LEDs The LEDs have the following meaning when flashing: Zone n+2 alarm: Automatic Alarm Signal Zone n alarm: Acknowledge available Cancel available Zone n supervisory: Reset available (green) Zone n+2 supervisory Future use Zone n trouble: Reset available (yellow) Zone n+2 trouble Future use Zone n+1 alarm: Signal Silence active Zone n+3 alarm Future use...
Editing MHI Databases Outputs Dialog 2.7.1 Overview The Outputs Dialog (see Figure 11) allows for the programming of the panel’s outputs and function relays. Figure 9 Panel Outputs 2.7.2 Outputs The Outputs section is a list box that is used to select the output to program. Once the output is selected, it is programmable for the following output types: •...
Editing MHI Databases 2.7.3 Relay Delay Relay Delay is the times that the relay waits before activating. A delay of 0 causes instant operation. This can be from 0 to 60 seconds. 2.7.4 Relay Duration Relay Duration affects the time the relay is activated. For relays operated from inputs, it is the minimum time the relay operates.
Page 31
Editing MHI Databases 2.8.4 Disconnect Disconnect sets the privilege level required for the Disconnect and Test Mode Hot Keys. These can be set to Level 1 (default) or Level 0. If Level 0 is chosen, the Disconnect Hot Keys can be operated without a passcode being entered into the panel. 2.8.5 Banner Mode Banner Mode dictates what the top line of the Main Menu of the LCD is.
Page 32
Editing MHI Databases 2.8.10 Bell Cutoff Bell Cutoff is the length of time the bells sound before they are automatically silenced by the panel. A time of 0 disables this feature. The cutoff can be set from 5 to 30 minutes. If the cutoff is used, it must be longer than the Bell Timeout.
Editing MHI Databases SYSTEM CONTROLS Acknowledge Signal Silence System Reset User Assigned Figure 11 Default Key Assignments Note: The fourth key is set to General Alarm by default. For non-Canadian installations, this key can be reconfigured. The keys and their functions are as follows: Action Silences the buzzer and acknowledges new troubles and alarms.
Page 34
Editing MHI Databases Action System Reset resets part or all of the system. The green LED flashes when the system, or part of the system, can be reset. The yellow LED flashes when there are conventional smoke detector circuits in alarm. Press System Reset to reset the smoke detectors.
Page 35
Editing MHI Databases Action Disables sounding of the bells. The buzzer beeps every 2 seconds while the bells are disabled. This beeping is suppressed while a privileged level is entered in the Signal panel. Press Signal Disconnect again to re-enable the bells. The red LED will flash Disconnect while the bells are disabled.
Editing MHI Databases Note: Networking is limited to two nodes for ULC applications. Action General Alarm See General Alarm on page 29 for information about this key. Configure one of the four remaining keys as Automatic Alarm Signal Cancel and label it as follows: AUTO ALM SIG CANCEL Automatic...
Editing MHI Databases The first number is the primary number, the second number is for a second monitoring station, and the third number is the backup number for the first number. The 1 and 2 Account Codes identify the system to the central station when a communication is sent.
Page 38
Editing MHI Databases number only if all attempts to communicate to the first telephone number fail. If all attempts to communicate to the third number also fail, a failure to communicate trouble will be generated. When Disabled is selected, the third telephone number is not used. The Dialing option has three different options for pulse or DTMF dialing.
Editing MHI Databases 2.8.20 Dialer Configuration 2 The Dialer Configuration 2 screen (seeFigure 15) contains the Swinger Shutdown Variables, Test Transmission options and Other Options. Figure 15 Dialer Configuration 2 The Swinger Shutdown options determine the maximum number of zone events and trouble events that the dialer will transmit in one day.
Editing MHI Databases 2.8.21 Call Directions The Call Directions dialog (see Figure 16) contains the options that determine which telephone numbers will be used to communicate events. Figure 16 Call Directions There are five different types of events that can each be sent to telephone number one or telephone number two.
Editing MHI Databases The Definition specifies the identifier of the alarm or trouble being sent to the central station. The zone types that are available are Fire, Sprinkler, Heat, Water and Untyped. The Reporting Codes are used when SIA or Contact ID is set to Programmed, or when using BPS formats.
Editing MHI Databases windows are nearly identical. Most controls on one are found on the other with the few exceptions noted. The current Circuit or Device is shown in the Title Bar of the window. Figure 19 Circuits Window Figure 20 Devices Window 2.9.2 Circuit List The Circuit List is located in the top left corner of the window.
Page 43
Editing MHI Databases 2.9.3 Circuit Type Selector The Circuit Type Selector is located below Circuit List on the left hand side. It is shown on the Circuit Window only. It is a drop down box used to assign the current circuit type. If the circuit is unused, select not assigned.
Page 44
Editing MHI Databases • Trouble: This function type is used for various circuit types and for control modules. Trouble type inputs operate LEDs only, no other outputs are allowed. This function type is assigned by MHI automatically. 2.9.6 Message The Message is located in the middle of the top of the window. This 3 line by 20 character text message is displayed or printed for all signals originating from the current input point.
Editing MHI Databases • Manual Restart: Check this to require that the control module not be reset by System Reset but by Manual Restart. Use of this option requires that there be a Manual Restart function key assigned to the panel. •...
Editing MHI Databases 2.10 Internal Circuits Window 2.10.1 Overview The Internal Circuits Window (see Figure 22) allows for the programming of outputs, LEDs, etc. for the various internal circuits (functions) of the Control Panel. Internal circuits 0, 71, 72, 73, 75, 81, and 82 are fire alarm functions while all others are trouble functions. All internal circuits have specific meanings and are stored in the archive of the panel.
Editing MHI Databases • Internal Circuit 99, Common Trouble: This circuit is tripped by any internal circuit or trouble condition not associated with an internal circuit that turns on the Common Trouble LED on the panel. This circuit is used to annunciate common trouble conditions at a remote location.
Editing MHI Databases • Verify List: Displays the Verify List. If there is no Verify List, a requester will appear asking whether you wish to perform a verification. See section 2.6.5 of the Modul-R Human Interface User Guide for a full description of the Verify List and its uses. 2.11 Relate Window 2.11.1 Overview The Relate Window (see Figure 23) allows for the relating of inputs, switches and groups to...
Editing MHI Databases selected for Fire Alarm type inputs. Use the <space> key or double click on the entry to cycle between available selections. Use the <Backspace> key in order to quickly reposition the current selection to another output. 2.11.5 Relays List The Relays List shows the general purpose function relays of the panel.
Mode Trouble occurs when logged in Level 2.) Higher Privilege Levels are reserved for Secutron's own use and are not discussed here. Certain functions can be assigned to different privilege levels. These functions default to the higher of the two privilege levels.
LCD Programming supervisory relay is not selected to be disconnected when the Common Disconnect hotkey is pressed. Pressing <Enter> causes the alarm relay to be not selected. COMMON DISCONNECT itle Options A S T Figure 25 Selector Screen For all screens, <Clear> returns to the previous menu level without changing any information and <Home>...
Page 52
LCD Programming press <Enter> to change. Select OK when done. <Clear> returns you to Program Menu without making changes. • Test Inhibit: View or change whether common relays are disconnected during Test Mode or not. <Clear> returns you to Program Menu without making changes. 3.3.3 Switches Menu This function can be set to Privilege Level 1 or 2.
Page 53
LCD Programming • Reset Max/Min: Clears the stored values for the maximum and minimum values returned by the addressable devices. These values are automatically cleared when the panel reboots. • Duplicates Check: This causes an immediate check to see if more than one device is using an address.
Page 54
LCD Programming • Test: Select devices to be tested. Test Mode must be active for this selection to be available. All devices selected for testing are automatically deselected when Test Mode is turned off. The Test Menu has the following options: -- ON: Select devices for testing.
Page 55
LCD Programming • SELECT: Change the Auto/On/Off state of relay. Each relay is shown in turn, showing the current state and allowing for it to be changed or the next relay to be displayed. Press <Clear> to stop viewing the relay list. •...
Page 56
LCD Programming -- Delay: Sets the length of time the panel will wait before reporting the GRID package off-line. This can be set from 10 to 255 seconds. -- Disconnect: If enabled, the Common Disconnect hot key will shut down Port 3. The GRID package will report the panel as offline.
Page 57
There is a special Level 2 passcode that is variable from day to day. It can be obtained from Secutron if the Level 2 passcode is forgotten. 3.3.11 Memory This function is restricted to Privilege Level 2. This menu has the following options: •...
Appendix A: Condition Codes and Zone Numbers Appendix A: Condition Codes and Zone Numbers Introduction This appendix lists the condition codes and zone numbers used by the panel. List of Codes and Zone Numbers 4.2.1 Condition Codes The alarm list and archive use the following formats for condition codes. Archive Alarm List Description...
Page 59
Appendix A: Condition Codes and Zone Numbers 4.2.2 Zone Number PPP:ZZ.SSS Format: Control Panel Number Panel Zone Panel Description Panel Description Zone Zone General Alarm Privilege Level Initiating Circuit 1 1st Stage Alarm Initiating Circuit 2 2nd Stage Alarm Network Verify Switch Comlink 1 Test Mode...
Page 60
Appendix A: Condition Codes and Zone Numbers Sub-Zone Number Zone Meaning of SubZone Number 000 - Wiring Fault Addressable Circuit All Others - Device Number Comlink 1 (Zone 51) Unit Network ID number Comlink 3 (Zone 53) Unit ID number Unit ID Number 1-8 MR-2614 Comlink 6 (Zone 54)
Page 61
Appendix A: Condition Codes and Zone Numbers Zone Meaning of SubZone Number 001 - Fire Drill 002 - Lamp Test 004 - Relay Disconnect 005 - Test Mode 006 - Signal Disconnect 007 - Acknowledge Hot Key Activation (Zone 90): Function Number of the Hot key 008 - Signal Silence pressed...
Page 62
Appendix A: Condition Codes and Zone Numbers Zone Meaning of SubZone Number 019 - Switch 4 On 020 - Switch 5 On 021 - Switch 6 On 022 - Switch 7 On 023 - Switch 8 On 024 - Switch 9 On 025 - Switch 10 On 026 - Switch 11 On 027 - Switch 12 On...
Page 63
Appendix A: Condition Codes and Zone Numbers Zone Meaning of SubZone Number 003 - port 3 006 - negative counter 008 - memory overflow 009 - co-processor memory overflow Network Reboot Required Why (Zone 95) 010 - network 011 - network 012 - network 013 - network All Others:...
A 4 A total bell load necessitates at least 6 A hour battery (in terms of 20 hour rating). The standard battery options available for the MR-2200 Control Unit are: a) 4 Ah internal, b) 7 Ah internal,...
Appendix C: Service Terminal General The MR-2200 Control Unit displays information and accept commands via the service terminal port. The information includes initiating circuit configuration, current status of bell, relays, etc., diagnostic information, the archive, etc. The commands allow for the selection of the information to view, limited programming and basic operation.
Page 66
Appendix C: Service Terminal Screen Name Description Displays the current battery level, and the current status of the battery and AC power. Also shows the timer for the battery test. Commands Battery Print battery calculation <Ctrl-B> Execute a dynamic battery test once and end 0<Ctrl-B>...
Page 67
Appendix C: Service Terminal Screen Name Description Displays the Archive History List. This is the list of the last 900 (approximate) events that happened. See Appendix A for a description of the condition codes and zone numbers. Commands Archive Page down Go to the end of the list Page up Go to the beginning of the list...
Page 68
Appendix C: Service Terminal Screen Name Description Shows the status of the Daylight Savings Time option & clock Clock calibration. This screen is restricted to Privilege Level 1 and above. This Tasks screen is for factory use only. This screen is restricted to Privilege Level 1 and above. Displays the FIFO memory usage of various system tasks.
Page 69
Appendix C: Service Terminal Screen Name Description For a single circuit, shows a grid displaying all the devices that are actually on the circuit. Commands Display next device (address)A Display selected device at address Type On-Line Reset Minimum/Maximum Values Energize both sets of terminals Energize only B terminals Energize only A terminals For a single circuit, shows a grid displaying all the devices that...
Page 70
Appendix C: Service Terminal Screen Name Description For a single circuit, shows a grid displaying the current Alarm, Early Warning, Supervisory and Trouble conditions for all devices on the circuit. Commands Display next device Alarms (address)A Display selected device at address Reset Minimum/Maximum Values Energize both sets of terminals Energize only B terminals...
Page 71
Appendix C: Service Terminal Screen Name Description Displays the analog values of 10 consecutive addresses for a single circuit. Commands Display next device (address)A Display selected device at address Analog Reset Minimum/Maximum Values Energize both sets of terminals Energize only B terminals Energize only A terminals Displays the Day/Night status, the default and manual sensitivities of all sensors on an addressable circuit.
Page 72
Appendix C: Service Terminal Command Description <Ctrl-V> Clear privilege (Set to User Privilege.) Set privilege. (code) is either the Level 1 or Level 2 (code)<Ctrl-V> passcode programmed into the panel. Print downloaded database. 90 ? Print archive. 99 ? Print configuration. <Esc>...
Appendix D: Table of Reporting Codes Appendix D: Table of Reporting Codes The following tables contain automatic Contact ID and SIA format reporting codes. Contact ID: The first digit (in parentheses) will automatically be sent by the control. The second two digits are to indicate specific information about the signal. For example, if zone 1 is a fire zone, you could program the event code as [1A].
Page 74
Appendix D: Table of Reporting Codes Table 1: Automatic Contact ID/SIA Reporting Codes (Continued) Reporting Code Code sent when... Dialer Contact SIA Auto Direction* ID Auto Rep. Codes Rep. Codes Dialer Bus NT-000/ Trouble/ Dialer Bus connection is lost/restored MA/R (3) 33 NR-000 Rest.
Page 75
Appendix D: Table of Reporting Codes Table 3: SIA Format Automatic Zone Alarm/Restore Codes Zone Alarm/Rest Rep. Supervisory/Rest. Rep. Trouble/Rest. Rep. Codes* Definition Codes* Codes* Fire FA-ZZZ/FH-ZZZ FS-ZZZ/FR-ZZZ FT-ZZZ/FJ-ZZZ Sprinkler SA-ZZZ/SH-ZZZ SS-ZZZ/SR-ZZZ ST-ZZZ/SJ-ZZZ Heat KA-ZZZ/KH-ZZZ KS-ZZZ/KR-ZZZ KT-ZZZ/KJ-ZZZ Water WA-ZZZ/WH-ZZZ WS-ZZZ/WR-ZZZ WT-ZZZ/WJ-ZZZ Untyped UA-ZZZ/UH-ZZZ...