supervisory relay is not selected to be disconnected when the Common Disconnect hotkey is
pressed. Pressing <Enter> causes the alarm relay to be not selected.
T
Options

Figure 25 Selector Screen

For all screens, <Clear> returns to the previous menu level without changing any information
and <Home> returns to the Main Menu without changing any information.
3.3

Menus

3.3.1 Clock Menu
This menu has the following options:
Date: View or change the date. The date is entered in MM.DD.YY format. Each section
of the date must be separated by a dot. Press <Enter> to accept date typed. <Clear>
removes any digits typed. If no digits are displayed, <Clear> returns you to the Clock
Menu. The new date is sent to all other panels on the Network, if used. All panels
assume this date. The date change is recorded in the Archive.
Time: Change the time. The time is entered in HH.MM.SS format. Each section of the
time must be separated by a dot. All times are in 24 hour format. Press <Enter> to
accept time typed. <Clear> removes any digits typed. If no digits are displayed,
<Clear> returns you to the Clock Menu. The new time is sent to all other panels on the
Network, if used. All panels assume this time. If <Enter> is pressed with no time
entered, the current time is sent to all panels on the network. If a change of greater than
5 minutes occurs, the new time is recorded in the archive.
i
1.The Master Panel in a network synchronizes all clocks in the network at
2.Changing the time while the panel is calibrating aborts the calibration.
• Calibrate: Calibrates the clock so that it keeps correct time. Calibration takes 2 to 45 days. Waiting
longer gives more accurate results. The panel functions normally while calibrating. When sufficient time
has passed, re-selecting this function asks for the correct time. The calibration is then be reported. In a
network, only the master panel needs to calibrated.
i
Note:
Changing the time using the Time option aborts the calibration. If a panel is
currently in a calibration, it ignores time changes sent over the network.
3.3.2 Common Relays Menu
This function is restricted to Privilege Level 2. The menu has the following options:
Disconnect: View or change the relays that can be disconnected by the Common
Disconnect hot key. Selected relays are marked by an asterisk (*). To change the
selection, move the cursor to the desired relay A(larm), S(upervisory) or T(rouble) and
COMMON DISCONNECT
itle
A S T
03:30 every day, sending both date and time.
LCD Programming
45