2.7.3 Relay Delay
Relay Delay is the times that the relay waits before activating. A delay of 0 causes instant
operation. This can be from 0 to 60 seconds.
2.7.4 Relay Duration
Relay Duration affects the time the relay is activated. For relays operated from inputs, it is the
minimum time the relay operates. The relay must stay on for this length of time before it can be
reset. This is for equipment that must remain off a length of time before it can be started up
again. If no input operates the relay, it is available for the reset of 4 wire devices. If the duration
is not 0 (zero), then the relay activates for the duration time when the Reset hot key is pressed
with neither of its LEDs flashing. The duration can be from 0 to 300 seconds (5 minutes).
2.8

Options Dialog

2.8.1 Overview
The Options Dialog (see Figure 12) allows for the programming of the panel and annunciator
options. These settings affect the current panel only.

Figure 10 Options Dialog

2.8.2 Buzzer Mode
Buzzer Mode sets when the panel buzzer sounds. Normal causes the buzzer to sound for new
supervisory and trouble conditions. All causes the buzzer to sound for all new conditions.
i
Note:
2.8.3 Bypass Priv
Bypass Priv. sets the privilege level required to set circuit and device bypasses, and manual
control of relays, control modules and switches. This privilege can be set to Level 2 (default) or
Level 1.
24
Always set this option to All (default) to meet current codes
Editing MHI Databases