2.8.20 Dialer Configuration 2
The Dialer Configuration 2 screen (seeFigure 15) contains the Swinger Shutdown Variables,
Test Transmission options and Other Options.

Figure 15 Dialer Configuration 2

The Swinger Shutdown options determine the maximum number of zone events and trouble
events that the dialer will transmit in one day. The trouble or alarm will still be displayed on the
panel and logged in the archive, but the dialer will not transmit the event. There are individual
counters for Zone Alarm and Restore, Zone Supervisory and Restore, Zone Trouble and
Restore and Maintenance Trouble and Restore. This feature will be reset at midnight. To
disable the feature, program 000.
The Test Transmission Time of Day determines when the automatic test transmission will
occur. The entry is four digits (HH:MM). To disable the feature, program the time as [9999].
The Test Transmission Cycle determines the number of days between test transmissions. This
is automatically set so that tests are performed daily and may not be varied.
i
Note:
If an upgraded database has a value other than 1, choose Set Default to reset the
value.
The TLM Trouble Delay controls the number of telephone line monitoring checks required
before a telephone line trouble is generated. The dialer checks the telephone connection at
10-second intervals.
The Maximum Dialing Attempts to Each Phone Number is the number of attempts that the
dialer will make to each telephone number before generating a fail to communicate trouble.
Post Dial Wait for Handshake is the amount of time the dialer will wait for a valid initial
handshake from the receiver after dialing the programmed telephone number.