2.4.6 Description
Description is a 20 character message that describes the Switch usage. This is useful in that
the switch now has a description of its usage that is easier to understand when assigning
Switches to Hot Keys.
2.4.7 Pushbuttons
There are five push buttons on the right side:
Exit: Close the Switches Window and return to the System Window. If there are any
invalid times entered (ie greater than 23:59), MHI requests corrections.
Reset: This removes all relates and all times for the currently highlighted switch.
Relate: Shows the Relate Window. Items marked *on* are operated/controlled by the
switch.
Map: Displays and/or updates the Map Window. See section 2.8 Map Window of the
Modul-R Human Interface User Guide.
Verify List: Displays the Verify List. If there is no Verify List, a requester will appear
asking whether you wish to perform a verification. See section 2.6.5 of the Modul-R
Human Interface User Guide for a full description of the Verify List and its uses.
2.5

Groups Window

2.5.1 Overview
The Groups Window (see Figure 7) is used for creating and editing the Groups of relates. The
Title Bar shows the current group.
This dialog allows you to setup "Groups" which are composed of a text description/message
and relates. Groups are a method of establishing zone representations. A zone representation
may include a message and/or a group of Relates. Inputs (ie. circuits and/or devices) may
relate to a Group or number of Groups and thus acquire all Relates that are referenced by
them. Inputs can also separately adopt the Group message. Making a change to a Group
affects all inputs (circuits and devices) related to the Group. This is a very powerful feature that
can significantly speed up the creation of medium to large size systems as well as simplify
changes. Forethought should be placed in defining appropriate Groups. Up to 250 groups may
be defined.